7.3.3 ST 1PS - ST 1PMS SET-UPS
7.4 SOUND
>
03
Evaporator
>
17
Electrical heater
>
CR
Heating cable
>
EL
Electric pump
>
FL
Flow meter
>
RB
Cock
>
PA
Well for anti-freeze probe
>
PF
Well for water inlet probe
>
03
Safety valve
>
RE
Tank electrical heater
>
Storage tank capacity
>
10
Bleed valve
>
02
Expansion tank
Unit size
12.1 15.1 20.1 22.1 25.1 30.1 32.1 34.1 35.1 40.1 45.1
Acoustic data LN version
Sound power level
(1)
dBA
72
73
73
74
74
82
82
82
82
84
84
Noise pressure level (10 m)
(2)
dBA
44
45
45
46
46
54
54
54
54
56
56
Acoustic data SLN version
(3)
Sound power level
(1)
dBA
69
70
70
71
71
79
79
79
79
81
81
Noise pressure level (10 m)
(2)
dBA
41
42
42
43
43
51
51
51
51
53
53
Unit size
50.1 55.1 60.1 75.1 35.2 40.2 45.2 50.2 55.2 60.2 75.2 80.2
Acoustic data LN version
Sound power level
(1)
dBA
84
84
86
86
86
88
88
88
88
90
90
90
Noise pressure level (10 m)
(2)
dBA
56
56
58
58
58
60
60
60
60
62
62
62
Acoustic data SLN version
(3)
Sound power level
(1)
dBA
81
81
83
83
83
85
85
85
85
-
-
-
Noise pressure level (10 m)
(2)
dBA
53
53
55
55
55
57
57
57
57
-
-
-
(1) Lw: sound power values in free field calculated in compliance with ISO 3744� Chiller working conditions (A35;W7)
(2) Sound pressure levels detected at 10/5/1 m from electrical panel, not channelled in free field, in compliance with ISO 3744� Chiller working conditions (A35;W7)
(3)SLN version have different dimension�