POM PDU 

per outlet monitoring & control 

 

User Manual 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for EG-PDU-007

Page 1: ...POM PDU per outlet monitoring control User Manual...

Page 2: ...Table of Contents 1 Introduction 1 2 PDU Package 2 3 Function 3 4 Installation 5 5 Web Interface 7...

Page 3: ...rue RMS current meter z Setup easily meter can read the IP address directly z Homepage support SSL z Provide per outlet power consumption z Provide audible alarm when the power consumption over the th...

Page 4: ...a Power Distribution Unit with supporting hardware and software The components of the package are z Power Distribution Unit z Rack mount Brackets z CD ROM it contains z User Manual z PDU Software z M...

Page 5: ...ing it can let the meter to show up the current information and temperature humidity in sequence z Press and hold the key after 2 beeping it can let the meter to show up the IP address z Press and hol...

Page 6: ...POM PDU User Manual Ver 1 0 4 ENV RJ11 for option ENV probe attached to detect temperature and humidity Circuit Breaker Overload power protection...

Page 7: ...air flow required for safe operation of the equipment is not compromised C Mechanical Loading Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to une...

Page 8: ...les of brackets with the notched hole on the vertical rail and attach with the retaining screws 6 Connect input and output power 7 Connect Ethernet cable to the PDU 8 Switch on the PDU Note 1 The defa...

Page 9: ...POM PDU User Manual Ver 1 0 7 5 Web Interface Login Input the PDU IP address in web browser Default ID is snmp Password is 1234...

Page 10: ...POM PDU User Manual Ver 1 0 8 Information PDU Display total PDU and each outlet power consumption When plug the option device ENV probe it will display temperature and humidity information...

Page 11: ...POM PDU User Manual Ver 1 0 9 Information System Indicate PDU system information including Model No Firmware Version MAC Address System Name System Contact Location...

Page 12: ...s and control outlet Select the outlet by checking the box and then click ON or OFF button to control output power for PDU ON Press the icon to turn on the assigned outlets OFF Press the icon to turn...

Page 13: ...outlets Setting Enter to the setting mode Outlet Assign the outlet in a group Note The outlet number needs to be input by the alphabetical order ON Press icon to turn on the assigned group OFF press i...

Page 14: ...week s day assigned day or every day Date When select sgl at column of Every need to input the truly date here Action Begin End ON Turn on outlet at this time None OFF Turn off outlet at this time No...

Page 15: ...m PDU Response 10 minutes PDU will ping the assigned IP address each minute one time if the equipment has not responded then number will be increased one time when the continual 10 minutes have not ob...

Page 16: ...l Ver 1 0 14 Configuration PDU Set the outlet name and delay time Name Rename the outlet ON Set delay time for power on sequential OFF Set delay time for power off sequential Note The maximum delay ti...

Page 17: ...POM PDU User Manual Ver 1 0 15 Configuration Threshold Set the warning and overload threshold for each circuit Set lower and upper threshold for temperature and humidity...

Page 18: ...POM PDU User Manual Ver 1 0 16 Configuration User Change ID and password Default ID is snmp and password is 1234...

Page 19: ...POM PDU User Manual Ver 1 0 17 Configuration Network PDU network information Enable DHCP Change the way to get IP address for PDU...

Page 20: ...ail Server only support to be input domain name not IP address Sender s Email Input the sender email address Email Address Input the recipient email address The message in the email Indicate OutletA H...

Page 21: ...NMP When event occurs PDU can send out trap message to pre defined IP address Trap Notification Set receiver IP for trap Community Set SNMP community Read Community is public and fixed Default Write C...

Page 22: ...DU User Manual Ver 1 0 20 Configuration SSL Enable SSL for web communication User must input the correct ID and password to enable SSL function The ID and password must be the same with the setting in...

Page 23: ...POM PDU User Manual Ver 1 0 21 Configuration Time Set the time for schedule control Internet Time Setting Get time from the assigned network time server System Time Input time manually...