ZŁ-4A is permanently controlling the voltage on the protected switchgear busbars. In
case when the voltage will drop below the level set in the settings, the voltage module “U<”
will be activated. A respective detection is made in central unit, and a proper message is sent
to all the bay units through CAN bus.
A pulsing message “UL” is shown on the front panels of bay units (Fig. 22). The device
changes its mode into “single criterion” mode. In such a situation a light detecting results in a
tripping signal generation.
Fig. 22 Voltage drop message.