Operating Manual
92
Arc fault
protection ZŁ-4A; (07.2019)
Register: UnitsConfig.Control
bit
7
6
5
4
3
2
1
0
-
-
AS3
AS2
AS1
AC
UP
UR
Bit number
Mnemonics
Description
7..6
-
Reserved
5
AS3
Registered bay unit tripping in zone S3
4
AS2
Registered bay unit tripping in zone S2
3
AS1
Registered bay unit tripping in zone S1
2
AC
Wrong bay unit network address
1
UP
Bay unit is available in the network
0
UR
Bay unit is registered in the system
Register: UnitsConfig.Status
bit
7
6
5
4
3
2
1
0
-
RL
SF
SS
RAS1
AS3
AS2
AS1
Bit number
Mnemonics
Description
7
-
Reserved
6
RL
Bay unit executive relay status
5
SF
Damaged optical sensors signaling
4
SS
Activated optical sensors signaling
3
RAS1
Signaling of remote tripping in zone S1
2
AS3
Signaling of tripping in zone S3
1
AS2
Signaling of tripping in zone S2
0
AS1
Signaling of tripping in zone S1
Register: UnitsConfig.SensorState
bit
7
6
5
4
3
2
1
0
-
-
-
-
P4
P3
P2
P1
Bit number
Mnemonics
Description
7..4
-
Reserved
3..0
P[4..1]
Logical state of optical sensor C[4..1]
Register: UnitsConfig.SensorSet
bit
7
6
5
4
3
2
1
0
-
-
-
-
P4
P3
P2
P1
Bit number
Mnemonics
Description
7..4
-
Reserved
3..0
P[4..1]
Optical sensor C[4..1] activation
Register: UnitsConfig.SensorFailure
bit
7
6
5
4
3
2
1
0
-
-
-
-
P4
P3
P2
P1
Bit number
Mnemonics
Description
7..4
-
Reserved
3..0
P[4..1]
Optical sensor C[4..1] damage
Register: UnitsConfig.SensorMode[Cx]
where x
– optical sensor number 1..4
bit
7
6
5
4
3
2
1
0
-
-
-
-
-
-
MxA
MxB
Bit number
Mnemonics
Description
7..2
-
Reserved
1..0
M[4..1]A, B
Optical sensor working mode C[4..1]
Summary of Contents for ZL-4A
Page 24: ...Operating Manual 24 Arc fault protection ZŁ 4A 07 2019 Fig 5 ZŁ 4A JC dimensions ...
Page 25: ...Operating Manual Arc fault protection ZŁ 4A 07 2019 25 Fig 6 ZŁ 4A JP dimensions ...
Page 26: ...Operating Manual 26 Arc fault protection ZŁ 4A 07 2019 Fig 7 ZŁ 4A JW dimensions ...
Page 61: ...Operating Manual Arc fault protection ZŁ 4A 07 2019 61 Fig 36 Page 2 STATUS using ...