Operating Manual
Arc fa
ult protection ZŁ-4A; (07.2019)
93
MxA, MxB
Cx optical sensor working mode
0 0
Inactivated
0 1
Optical sensor Cx tripping in zone Z1
1 0
Optical sensor Cx tripping in zone Z2
1 1
Optical sensor Cx tripping in zone Z3
Register: UnitsConfig.FlashTestStatus
MxA, MxB
Optical sensors test status
0 0
test has not been performed
0 1
test performed but the sensor not checked (off in the bay unit)
1 0
test performed but the sensor damaged
1 1
test performed and the sensor operational
bit
7
6
5
4
3
2
1
0
C4A
C4B
C3A
C3B
C2A
C2B
C1A
C1B
Summary of Contents for ZL-4A
Page 24: ...Operating Manual 24 Arc fault protection ZŁ 4A 07 2019 Fig 5 ZŁ 4A JC dimensions ...
Page 25: ...Operating Manual Arc fault protection ZŁ 4A 07 2019 25 Fig 6 ZŁ 4A JP dimensions ...
Page 26: ...Operating Manual 26 Arc fault protection ZŁ 4A 07 2019 Fig 7 ZŁ 4A JW dimensions ...
Page 61: ...Operating Manual Arc fault protection ZŁ 4A 07 2019 61 Fig 36 Page 2 STATUS using ...