Arc fault
protection ZŁ-4A; (07.2019)
12.3. Executive unit configuration
In order to enter into the “configuration” mode press
button for 3 s. After that the con-
figuration menu will be displayed (see Fig. 30)
Fig. 30
“Configuration” mode.
The following parameters can be set in the configuration mode:
executive unit network address (ranged 1....5).
12.4. Error messages
In case when a executive unit will detect wrong operation of the device error number will
be shown on the display.
„E1”
no communication with the central unit. The executive unit will not generated a tripping
signal.
„E2”
not applicable.
„E3
an executive unit has its network address configured incorrectly. A physical connection
through CAN interface is correct. It is necessary to register this executive unit in the central
unit. “ERROR” LED is not lighted.
„E4”
an executive unit does not have either a network address or a serial number assigned.
The “ERROR” LED is not lighted.