Operating Manual
Arc fa
ult protection ZŁ-4A; (07.2019)
59
13.3.2. Page 2) STATUS
Information about current status of the protection is displayed on this page
The following submenus are available:
Submenu “ZONES STATUS”
After selecting this submenu by pressing
button the user receives information about the
amount of JP which have the optical detector configured for working in the specified zones.
When the submenu is selected by pressing
button it is possible to obtain information
about network addresses of the units with the optical detectors assigned to the specified
zone. When the JP network address is selected (by pressing
button), it is possible to ob-
tain detailed information about the present status and configuration of JP. Selecting the next
subpages takes place by pressing
button. The next JP is selected by pressing the
button.
ZONE S1 : 00
– it shows information about the amount of the units with the optical
detector assigned to zone 1,
ZONE S2 : 00
– it shows information about the amount of the units with the optical
detector assigned to zone 2,
ZONE S3 : 00
– it shows information about the amount of the units with the optical
detector assigned to zone 3.
Submenu “JC UNIT RELAYS : 00”
This submenu shows the amount of the JC activated executive relays. After selecting this
submenu by pressing
button the user receives detailed information about a status of the
JC executive relays.
“Z: JC UNIT RELAYS”
The executive relays are denoted by symbols from P1 to P6. The present relay status is dis-
played below the relay name. The following executive relays statuses are possible:
“0” relay contact is opened,
“1” relay contact is closed.
In case when the relay is activated, i.e. its status is “1”, the user has an opportunity to get
information about which JP units have generated a signal for the relay activation. In order to
obtain such information please select relay number (P1-P6) by pressing
button and then
confirm your choice by pressing
button. Next, the page “RELAY Px“ (where “x” denotes
the relay number) with the list of JP network addresses will be shown the LCD display.
Summary of Contents for ZL-4A
Page 24: ...Operating Manual 24 Arc fault protection ZŁ 4A 07 2019 Fig 5 ZŁ 4A JC dimensions ...
Page 25: ...Operating Manual Arc fault protection ZŁ 4A 07 2019 25 Fig 6 ZŁ 4A JP dimensions ...
Page 26: ...Operating Manual 26 Arc fault protection ZŁ 4A 07 2019 Fig 7 ZŁ 4A JW dimensions ...
Page 61: ...Operating Manual Arc fault protection ZŁ 4A 07 2019 61 Fig 36 Page 2 STATUS using ...