6
1.6 Clearances to Combustible Surfaces
It is of the utmost importance that the installation conform to the minimum
clearances to combustible surfaces (Material made of or surfaced with wood, compressed
paper, plant fibers, plastics, or other material that can ignite and burn, whether flame proofed
or not, or whether plastered or unplastered). Consult applicable codes and regulations for
precedence. Non-compliance to minimum clearances may result in fire, explosion, personal
injury or death. The U.L. Listing specifies: “For all boilers rated for 50 psi or less and for all
water boilers, installation clearances are Form I
II.” & “The boilers are intended for installation
on noncombustible flooring.” The clearances for each model follow:
EL-200B
EL-375B
EL-500B
Top & pipe connections
18"
18"
18"
Front - (burner location)
48"
48"
48"
Sides
18"
18"
18"
Rear
18"
18"
18"
Flue Pipe
18"
18"
18"
Bottom
Must be on non-combustible flooring.
Model
Minimum clearance from:
48” Front
18” Sides, Top
and Rear
18” Flue Pipe
Non-combustible Flooring
Minimum Clearances
Call 1-
800-347-9575
for Technical Support