53
Call 1-
800-347-9575
for Technical Support
11. Depress the manual reset button. After depressing the reset button, the green and red
lights will flash simultaneously four (4) times. The green light will remain on, and the red
light will turn off. The boiler will be ready for operation provided there is water on the
probe.
EL-200B
EL-375B
(EL-500B is
similar)
Low Water Cut
Off Control
Location of LWCO
EL-200B
EL-375B
EL-500B
To Remove the Probe