71
Call 1-
800-347-9575
for Technical Support
5. See Metering Pump Assembly
Testing Procedure in Section 9.3
If Metering Pump Assembly Tested Good,
go to next Component. Otherwise
repair/replace necessary components
6. (SKIP - for gravity fed Pumps
w/plenty of fuel) Check for Air Leaks:
Check all fittings from the pump back to
the tank for suction side air leaks (make
sure pipe sealant is used for all threaded
connections). Inspect for cracked flares,
tighten fittings and look for cracked
lines. If you see no evidence of leaks,
try soap and air pressure test on the
suction side lines by pressurizing at the
inlet through the 3/8 inch copper line
that leaves the fire-stop valve at the
tank.
Yes - Repair/Replace leaking component(s)
No - Go to Next Component
Tank/Tank
Controls
1. In the tank from which the metering
pump is supplied, is the fuel pickup
submerged into the oil source?
Yes - Go to Next Action/Question
No - Fill Tank
2. Is there continuity across the wires
for the Low Level Cutoff Switch?
Yes - Go to Next Action/Question
No - Replace Switch
3. Check wire connections from Switch
to thermostat plug on primary control.
Are all connections properly secured?
Yes - Go to Next Component
No - Repair connections