b. With an amp clamp (must have mA AC capability)
i. With burner plug unplugged, run wire from spring to spring of the
transformer.
ii. Plug in the burner and apply jumpers as in step 11.
iii. Using the amp clamp around the wire, read the amperes.
1. Reading should be between 20mA and 26mA with a nominal of
23mA. (transformer should be labeled)
13.
Remove jumpers from T-T and F-F terminals.
14.
Unplug the burner plug from its receptacle.
15.
Return the Transformer and Primary Controller to its operating position and plug in the
burner.
16.
Open the hand valve on the preheater, and plug it in.