89
Call 1-
800-347-9575
for Technical Support
10.2 Boiler Specifications
Specification Table:
Multi-Fuel Burning Appliance
Model Number
Model EL-200B
Model EL-375B
Model EL-500B
Bonnet Capacity
Output BTU
160,000 BTU
300,000 BTU
400,000 BTU
Fuel Input
1.4 GPH
2.7 GPH
3.6 GPH
Nozzle Only
No. 30609-5
No. 30609-28
30609-28
Fuels
ASTM D396 No. 2 oil fuel,
Used Crankcase Oil, and
Used Automatic
Transmission fluid
ASTM D396 No. 2 oil fuel,
Used Crankcase Oil, and
Used Automatic
Transmission fluid
ASTM D396 No. 2 oil fuel,
Used Crankcase Oil, and
Used Automatic
Transmission fluid
Designed Outlet
Water
Temperature
250°F Maximum
250°F Maximum
250°F Maximum
Flue Draft
-0.05" WC
-0.05" WC
-0.05" WC
Atomizing Air
Pressure
9-11 PSI
13-15 PSI
13-15 PSI
Circulator Pump
To fit application
To fit application
To fit application
Maximum Fuse
Size
25A
25A
25A
Burner Motor
1/5 HP, 115V/60Hz, 3.3A
1/4 HP, 115V/60Hz, 3.5A
1/4 HP, 115V/60Hz, 3.5A
Metering Pump
Motor
15Watt, 115V/60Hz, 0.35A
15Watt, 115V/60Hz, 0.35A
15Watt, 115V/60Hz, 0.35A
Ignition
Transformer &
Control Circuit
115V/60Hz, 2.0A
115V/60Hz, 2.0A
115V/60Hz, 2.0A
Oil Preheaters
115V/60Hz, 2.5A Maximum
115V/60Hz, 3.5A Maximum
115V/60Hz, 3.5A Maximum
Minimum
Clearance to
Combustible
Surfaces
Top & pipe connections-18"
Front - 48" (burner end)
Sides - 18"
Rear - 18"
Flue Pipe - 18"
Bottom – must be on non-
combustible flooring.
Top & pipe connection -18"
Front - 48" (burner end)
Sides - 18"
Rear - 18"
Flue Pipe - 18"
Bottom – must be on non-
combustible flooring.
Top & pipe connection -18"
Front - 48" (burner end)
Sides - 18"
Rear - 18"
Flue Pipe - 18"
Bottom – must be on non-
combustible flooring.
For commercial and industrial use only.