© 2018 EnergyLogic, LLC Toll Free: 800 311 8828 Fax: 615 471 5202 www.energylogic.com 34
Rev. Date 062718
7/32”
2.1 Fixed Angle Mount
Motor & Extension Tube
30 ft-lbs
30 ft-lbs
[41 N-m]
9/16”
Power Cable
Stranded Sheilded CAT5e Cable
Safety Cable
Power Cable
Stranded Shielded CAT5e Cable
Safety Cable
The power cable must be opposite
of the safety and CAT5e cables
7/32”
NOTE
: Power cable must be routed into the mount on the
opposite side from safety cable and CAT5e cable.
CAT5e Shielded must be used
at a minimum. No unshielded
communication cables.
The communications cable
MUST
be routed at least 1 foot away from
power cables, high voltage power
wires, and fluorescent lighting.
The only point where the power
cable should be near the comm
wire is when they are in the mount
and extension tube.