Code
Name
Code
Type
Factory
Setting
Description
Symptoms
Troubleshooting Tips
1028
Hall Error
Fan Will Not
Start
Fan Will Not
Complete Blade
Detect
Fan “Twitches”
Fan Runs
Irregularly
Confirm that hall sensor is properly
plugged into the drive
1029
Receive Frame
Error / Noise On
Comm Lines
Fan Stops
Fan Will Not
Start
1. Confirm whether touchpad was
unplugged or not
2. Confirm that CAT5 is under 100ft
3. Confirm that CAT5 is from factory and
has not been modified
4. Confirm that CAT5 is shielded
5. Confirm that repeaters are properly
installed on the network
6. Double check network splices
7. Plug touchpad directly into board
8. Confirm firmware is 146 or above
COMM
ERROR
Fan Stops
Fan Will Not
Start
1. Confirm whether touchpad was
unplugged or not
2. Confirm that CAT5 is under 100ft
3. Confirm that CAT5 is from factory and
has not been modified
4. Confirm that CAT5 is shielded
5. Confirm that repeaters are properly
installed on the network
6. Double check network splices
7. Plug touchpad directly into board
8. Test for 5VDC on blue pair if screen
lights up, test for 24VDC if screen does
not light up
Troubleshooting
For all other fault codes, please call Technical Support at (800) 351-0643.