SENSOR DIMMER SWITCH
OCCUPANCY / VACANCY
Max. 12'
on the sides
Max. 30'
from front
Detection Range
Installation
Height: 4' - 5'
1. Connect RED wire from sensor to the LOAD wire.
2. Connect BLACK wire from sensor to the HOT wire.
3. Connect GREEN wire from sensor to the GROUND wire.
4. Cap the Blue wire.
LED Indicator
1
2
3
4
1
2
3
4
RANGE
LIGHT
TEST
TIME
10
Min
20
Min
Min
30
Red
Load
CFL 150W
LED 150W
INC/HAL 600W
Hot
Neutral
120Vac 60Hz
Black
Green
Ground
3-Way Wiring with 57302-3K Remote Dimmer
Blue (Signal)
57302-3K*
Black to Load
Red
Hot
Neutral
Black
Blue (Signal) Blue (Signal)
Green
Ground
Green
Ground
Red
Load
120 VAC
60Hz
Single-Pole Wiring
57302-3K *
Red
Black
to Load
Hot
Neutral
Black
Blue
Green
Ground
Green
Ground
Red
Load
120 VAC
60Hz
Blue
Green
57302-3K*
Blue Blue
Red Red
Black
Ground
*Optional remote dimmer 57302-3K sold separately
4-Way Wiring with Two 57302-3K Remote Dimmers
FACE COVER REMOVAL
Gently remove the face cover using a flat blade screwdriver. Find the slots at
the bottom left or right of the panel cover and pry the panel cover loose.
Face Cover
Fresnel Lens
UP Button
DOWN Button
WARNING
Turn the POWER OFF at the circuit breaker before installing the
sensor
Read and understand these instructions before installing. This device is
intended for installation in accordance with the National Electric Code and local
regulations. It is recommended that a qualified electrician performs this
installation. Make sure to turn off the circuit breaker or fuse(s).
Use copper wires only.
DWODS-120
TIME DELAY ADJUSTMENT
WIRING DIRECTIONS
SPECIFICATIONS
DESCRIPTION
The DWODS-120 has a 180° detection range with a maximum distance
of 30’ detection in front of the sensor and 12' on the sides providing
10
00 sq. ft.
of coverage. For maximum results, the sensor must be properly installed
between the height of 4’ to 5’ and away from obstructions such as walls,
furniture and transparent barriers like Low-E glass.
Time Delay.....................................................15Sec, 10, 20, and 30Mins
The DWODS-120 sensor dimmer switch uses advanced passive infrared sensor
to detect heat emitted motion. The sensor switch can turn on a load and keep it
on as long as it detects motion. The dimmer works just like our 5
7302
dimmer,
gradually turning lights on and off, allowing your eyes to adjust to the new light
level. Use the rocker to adjust the light level for any activity, or set the preset
level to ensure lights always turn on to your desired light level. The sensor will
automatically shut off the load at the end of the selected time delay. The
countdown of the selected time delay starts after the last motion detected.
Default Light Level..........................................................30 Lux--Daylight
Operating temperature......................................32°F~104°F(0°C~40°C)
Voltage............................................................................120VAC, 60Hz
Tungsten/Incandescent.................................................................600W
COVERAGE
Electronic self-ballasted(LED)............................................150W(1.25A)
Located on the left, this switch adjusts the time delay.
Default position: 15 Seconds (Test mode)
Selectable: Test (15secs), 10, 20, and 30mins.