INSTALLATION INSTRUCTIONS
SPECIFICATIONS
DESCRIPTION
3
WARNING
Turn the POWER OFF at the circuit breaker before installing the
sensor
Read and understand these instructions before installing. This device is
intended for installation in accordance with the National Electric Code and local
regulations. It is recommended that a qualified electrician perform
s
this
installation. Make sure to turn off the circuit breaker or fuse(s) and make sure
power is off before wiring the device.
Use copper wires only.
WIRING DIRECTIONS
As illustrated in Figure 1, The
MWOS
has a 180°
PIR
detection range with a
maximum distance of 40’ detection in front of the sensor
and 20' on the sides
for a total of 1200 s.f
.
The Ultrasonic detection range is 20' in the front and 10'
on the sides for a total of 400 s.f.
For maximum results, the sensor must be
properly installed between the height of 4’ to 5’ and away from obstructions
such as walls, furniture and transparent barriers like Low-E glass.
The MWOS is a Multi-Technology Wall Sensor Switch that combines advanced
passive infrared (PIR) and ultrasonic technologies to help avoid false triggering.
Selectable operating modes allow the sensor to turn a load on, and hold it on as
long as either or both technologies detect
motion. The sensor will automatically
shut off the load at the end of the selected time delay. The countdown of the
selected time delay starts after the last motion detected. The sensor is
customizable with dials that can adjust
Time Delay
, detection
Range
, ambient
Light Level
, and
switch
es
to change between
Occupancy/ Vacancy
mode
s
and select PIR/ Ultrasonic modes and levels.
1.
Connect RED wire from sensor to the LOAD wire.
2.
Connect BLACK wire from sensor to the HOT wire.
3.
Connect WHITE wire from sensor to the NEUTRAL wire.
The
NEUTRAL
WIRE IS REQUIRED.
4.
Connect GREEN wire from sensor to the GROUND wire.
ADJUSTMENT
MWOS
Multi-Technology PIR/Ultrasonic
Occupancy / Vacancy Sensor Switch
Incandescent ...................................
................
...............
.
.......
800VA@120VAC
Time Delay.............................
...............
......................
.
.......…… 15Sec to 30Mins
Light Level.............................
...............
....................
.
...............
.
..
10
0 Lux--Daylight
Fluorescent
/
Ballast...............
................
.
.......800VA@120VAC /1600VA@277VAC
Operation Temperature................
................
...................................
.
32
°
F--131
°
F
Voltage ................................................
...
.
.............
............. 120/277VAC,
50/
60Hz
Motor .......................................
...............
..................
.
..........................…… 1/4Hp
COVERAGE
Figure 1
PIR:
Max. 40'
in front
and 20' on sides
Installation
Height: 4' - 5'
The control panel cover is also the push button on the switch.
Remove the
push-button
cover plate
by prying from the bottom of the
push-
button and
pulling outward.
Ultrasonic Sensitivity Dial
Default position: Center at 65%
Adjustable: 30% (Position 1) to 100% (Position 4)
•
Note: Turn toward right for greater room space. Turn toward left to
avoid false alert in smaller room and near the door way or heat
source.
Light dial
The sensor may be adjusted to operate at the desired level of ambient light.
•
To do so, turn the dial to point the arrow toward the “-”sign for sensor to
detect motion and operate during low light or no light. Point the arrow
toward the “+”sign for sensor to operate when there’s more light in the
area or even during daylight.
Ultrasonic:
Max. 40'
in front and 20' on sides
Neutral
White
Hot
Black
Ground
Green
Load
Red
Neutral
Load
Figure 2
White
OFF OCC VAC
1
ULTRASONIC
4
2
3
1
4
2
3
LIGHT
OFF OCC VAC
Figure
4
Push Button/
Control Panel Cover
Mounting Yoke
ULTRASONIC
LIGHT
PIR Lens
Ultrasonic Cones
Detection LEDs
Red=PIR
Blue=Ultrasonic
ON
OFF
1 2 3 4 5 6 7
Detection Range
Figure