MODEL 13800 User Guide 

10 

N or n

 

Invoke and display PSG Network Adapter neighbor 

count (see next section) 

X or x

 

Enable/disable ASCII responses.  Used to squelch any 

ASCII asynchronous responses (i.e. send only binary 

mode).  This is reset by command 

R

 

Note: PSG Network Adapter transmits certain status 

messages asynchronously, unless the X command has 

been issued: 

 

Line Break Detected 

 

RF COMMUNICATION TEST

 

For proper operation, the PSG Network Adapter should be placed 

within RF range of 

at least 

one other 

EnernetWorks™

 node. 

For maximum reliabilty it should link to at least four neighbors.  

The following test requires connection to a network interface 

device (see previous section, TESTING): 

1. 

Make sure Configuration / Building address is set per 

instructions on page 6, 

Configuration Switches.

 

2. 

If you are using the monopole helical antenna (standard 

supplied configuration) place the PSG Network Adapter 

in its proposed location.  Then go to step 4. 

3. 

If you are using the dipole/cable antenna option, place 

only the antenna in its proposed location.  Screw the 

other end of the cable to the PSG Network Adapter 

antenna connector. 

 (WARNING: HAND TIGHTEN 

ONLY, DO NOT USE TOOLS.  Excessive force can 

damage the connector!)

 

4. 

Issue the “N” command to send a 

neighbor count

 

command on the mesh network.  PSG Network Adapter 

responds with the message 

Neighbor Count = XX, 

where XX is the actual number of 

EnernetWorks™

 

nodes heard. 

 

5. 

If the Neighbor Count is less than 4, consider relocating 

the PSG or antenna closer to other 

EnernetWorks™

 nodes.

 

Summary of Contents for 13800

Page 1: ...Pub No 13801 022709 ENERNET Corporation Copyright 2009 Model 138 Programmable Serial Gateway EnernetWorks Network Adapter ...

Page 2: ...E IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE THIS MANUAL MAY CONTAIN TECHNICAL INACCURACIES AND OR TYPOGRAPHICAL ERRORS CHANGES ARE PERIODICALLY MADE TO THIS MANUAL WHICH ARE INCORPORATED IN LATER EDITIONS ENERNET CORPORATION MAY MAKE CHANGES AND IMPROVEMENTS TO THE PRODUCT S AND OR PROGRAMS DESCRIBED IN THIS PUBLICATION AT ANY TIME WITHOUT NOTICE IN NO EVENT WILL EN...

Page 3: ... device The required antenna impedance is 50 ohms To reduce potential radio interference to other users the antenna type and its gain should be so chosen that the equivalent isotropically radiated power e i r p is not more than that permitted for successful communication FCC ID TGD13800 IC 6120A 13800 This device complies with Part 15 of the FCC Rules Operation is subject to the following two cond...

Page 4: ...ial device connects to the PSG Network Adapter A single model 138 Programmable Serial Gateway Network Adapter can accommodate data traffic from as many as 500 EnernetWorks capable nodes MESH NETWORK OVERVIEW A simple overview example of EnernetWorks is shown in Figure 1 A network interface device communicates with an arbitrary number of targeted EnernetWorks capable nodes via one or more PSG Netwo...

Page 5: ...stat Control Node RF PLC Repeater RF PLC Repeater RF PLC Repeater Building Electrical wiring Thermostat Control Node Thermostat Control Node Thermostat Control Node Thermostat Control Node Thermostat Control Node Thermostat Control Node Thermostat Control Node Thermostat Control Node Thermostat Control Node Model 138 2nd Gateway RS232 RS232 Ø N Network Interface ...

Page 6: ... fashion See Figure 3 for Configuration Switch location and Table 1 for address setup If the selected network address is already in use the Network Adapter will light the Service LED indicating possible network contention Decimal S1 S2 S3 S4 S5 S6 S7 S8 0 DN DN DN DN DN DN DN DN 1 DN DN DN DN DN DN DN UP 2 DN DN DN DN DN DN UP DN 3 DN DN DN DN DN DN UP UP etc DN DN DN DN DN UP DN DN Table 1 MULTIP...

Page 7: ...DEL 13800 User Guide 7 Figure 2 Network Adapter Programmable Serial Gateway ANT CONNECTOR Wall Plug 9 Pin Serial cable ANTENNA P N ANT 916 CW RH NETWORK ADAPTER SERVICE CONFIGURATION NETWORK EIA 232 POWER ...

Page 8: ...13800 User Guide 8 Figure 3 Network Adapter Configuration Switches and Service Pin Button NOTE The orange two pin connector labeled NETWORK is not used 1 2 3 4 5 6 7 8 SERVICE CONFIGURATION NETWORK BUTTON LED ...

Page 9: ...device to 57600bps 8 bits no parity 1 stop bit flow control NONE 4 Connect 9 pin serial cable to the PSG Network Adapter EIA 232 port and to your network interface device 5 Connect power cable to PSG Network Adapter It immediately sends the message EnernetWorks Serial Gateway Ver firmware version 6 You can now execute the following PSG Network Adapter commands as needed CMD Display firmware versio...

Page 10: ...ee previous section TESTING 1 Make sure Configuration Building address is set per instructions on page 6 Configuration Switches 2 If you are using the monopole helical antenna standard supplied configuration place the PSG Network Adapter in its proposed location Then go to step 4 3 If you are using the dipole cable antenna option place only the antenna in its proposed location Screw the other end ...

Reviews: