5.0
5.0 Operation
Operation
5.1
5.1 Panel Status
Panel Status
Bright front panel LEDs allow the overall status of the panel to be
determined at a glance�
5.1.1
5.1.1
Front Panel LED Identification
Front Panel LED Identification
The HDX product provides status information illuminated LED on the
front of the panel (see Figure 4)�
A Power Input
This LED will illuminate BLUE when power is present on the A input�
B Power Input
This LED will illuminate BLUE when power is present on the B input�
Breaker Trip/Alarm
This LED will illuminate RED if a breaker has tripped or any other alarm
condition exists� Under normal operating conditions it is not illuminated�
5.2
5.2 Breaker Inventory (HDX
Breaker Inventory (HDX
™
™
ABC 10 Model)
ABC 10 Model)
Upon first power up there will be a red LED flashing to indicate breaker
inventory needs to be performed� Anytime the circuit breaker compliment
is changed, you will need to update the breaker inventory for correct
monitoring of breaker status�
Step 1.
Lift the breaker compartment door� Turn on any circuit breakers
you wish to have monitored�
Step 2.
Press and hold the blue button (See Figure 5 for breaker
inventory button location)� Hold the button until the red BREAKER
INVENTORY LED turns on and subsequently turns off. This
should take about 5 seconds�
Step 3.
Breaker inventory will remain in the controller memory even if
power is lost�
NOTE: If a new breaker is installed and turned on after an inventory has
been taken, it will cause an alarm until the breaker inventory is updated�
5.3
5.3 Breaker Inventory (All Other Models)
Breaker Inventory (All Other Models)
Anytime the circuit breaker compliment is changed, you will need to
update the breaker inventory for correct monitoring of breaker status�
Step 1.
Lift the breaker compartment door� The circuit board on the inside
of the door has a series of dip switches that are used to inventory
breakers� Each switch is labeled with a silk screen on the board
indicating which channel the switch will inventory�
Step 2.
Locate an arrow printed near the dip switch labeled "IN"� To
inventory a breaker press the dip switch so that side facing the
"IN" arrow is depressed� In Figure 6, A1 and A2 (switch 1 and 2)
are inventoried breakers� A3 and A4 (switch 3 and 4) are not in
inventory�
Figure 4. HDX Front LED Status Indicators
Figure 5. Breaker Inventory Button and LED