7. Connect shorter black cable (with two wires) on the negative (-) terminal of battery #2.
8. With the multimeter in DC range (200V), measure the DC voltage between negative (-) terminal of battery #2
and positive (+) terminal of battery #4 should be between 24-27Vdc with good batteries. Ensure that the voltage
polarity is correct.
-
+