Figure 27 — UPS Maintenance: Relay and Load Shed Screen
UPS Maintenance > Relay and Load Shed:
The Alpha Micro 100 has two dry contacts (C1 and C2) on
the front panel which can be configured by the user to open or close based on the specific trigger conditions. See
for a description of all available dry contact functions.
C3-C6 not available on
the Alpha Micro 100.
Inverter Cutoff Threshold
Defines the point where the unit will switch from Inverter to Standby when the battery is considered to be low or
in order to preserve the battery.
The inverter cutoff threshold is configurable in 0.1Vdc increments according to the battery voltage as described
in the following table.
24Vdc Battery
Parameter
Default
Minimum
Maximum
Inverter Cutoff (Vdc)
21.5
21.5
23
Battery Low Warning Threshold (Vdc)
Vset + 1