9.5.9 Communications
Configure TCP/IP
See section "9.5.1 Installation and Set Up" on page 38.
Configure SNMP
Configure SNMP is used to set the UPS for use with SNMP communications.
Figure 42 — Configure SNMP Screen
Figure 43 — Email Notification Screen
Email Notification
Enabling Email Notification sends an email message whenever selected UPS events happen. (See page 52 to
configure logged events.)
To create up to 4 different destinations, click
Add Destination
and then fill in the required fields:
• Enter a
To
address.
• Check off at least one of the
Notify
boxes.
• CC
and
Subject
fields are optional.
To edit an existing destination, select the destination by clicking on it.
To remove a destination, click on the destination and click
Remove Destination
.
NOTE:
The FXM communications module does not pass authentication details to the SMTP server. You must
enable anonymous authentication in the SMTP server to allow the FXM to email anonymously.
NOTE:
Email destinations can only save up to 63 characters. More than 63 characters can be typed, but
only the first 63 characters will be saved.