background image

 

For more information visit www.alpha.com  

Page 1 of 3 

 
 

Copyright © 2019 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies. 

0470452-TAB Rev A (04/2020) 

Other product names mentioned in this document may be registered in certain jurisdictions. Information is subject to change without notice.

 

 

F-MKT-04 Rev 1.4 

TECHNICAL ADVISORY BULLETIN 
Recommended Grounding for TE33-1820 Pole Mount RPN Enclosure   

 
Date: 4/21/2020 
Model #: 

TE33-1820 Remote Power Node Enclosure  

 

Issue 

 

As there are a few configurations of the TE33-1820 RPN, additional information on grounding is 
required beyond what is already provided in the installation manual.  

Corrective Action 

 

Provide  detailed  grounding  instructions  with  a  diagram  for  the  pole  mount  TE33-1820  RPN 
enclosure.  

 

The  grounding  specifications  and  diagram  depicted  in  this  TAB  are  based  on  recommended 
industry best practices. However, site grounding design and construction shall always adhere to 
local electrical codes and the internal standards of the company that is responsible for ownership 
and operation of equipment. 

 

Warning  

 

Only  qualified  personal  should  install  and  connect  the  power  components  within  the  Alpha 
system. 

 

 

An enclosure that is not properly grounded presents an electrical hazard and will likely result in 
premature equipment failure.

  

 

A  proper  grounding  system  (i.e.  ground  electrode  system)  that  meets  or  exceeds  the 
specifications of the equipment must be designed and installed prior to or in conjunction with 

the installation. The ground system must be bonded to the enclosure to ensure a “common” or 
“single

-

point” ground.

 

 
 
 
 
 
 
 
 
 
 
 
 
 

Reviews: