Grounding Instructions  
 

1.

 

Install a 

continuous

 length of #6AWG tinned solid copper ground wire (grounding electrode 

conductor) connecting the two driven ground rods and terminate it on the ACEG bus in the 
AC service disconnect enclosure.  This length of conductor serves as a Vertical Ground Riser 
(VGR) (

Refer to Figure 1)

Note: 

It is recommended that 

all buried grounding connectors are 12” below finished grade 

line or below the frost line

For below grade connections, crimp or mechanical connectors may 

be used instead of an exothermic weld provided they are listed for direct burial applications.

 

 

 

 

 

 

 

 
 

 

 
 
 
 

 

 

 
 

 
 
 
 
 
 
 
 
 
 

Figure 1 

 TE33-1820 RPN Grounding Diagram

 