2.
Route a length of #6 AWG tinned solid copper conductor from a junction point with the VGR
at a location below the cabinet to the Enclosure MGB, located on the right-side wall. Connect
the length of conductor to the VGR via an irreversible compression connector or exothermic
weld and connect the other end to the Enclosure MGB using a suitable two-hole compression
lug. The enclosure MGB accepts a two-
hole lug with 3/8” holes on 1” centers
(refer to Figure
2).
Note:
Avoid tight radius bends and route the conductor such that it intersects with the VGR in
a downward manner as illustrated in Figure 1.