2.

 

Route a length of #6 AWG tinned solid copper conductor from a junction point with the VGR 
at a location below the cabinet to the Enclosure MGB, located on the right-side wall.  Connect 
the length of conductor to the VGR via an irreversible compression connector or exothermic 
weld and connect the other end to the Enclosure MGB using a suitable two-hole compression 
lug.  The enclosure MGB accepts a two-

hole lug with 3/8” holes on 1” centers 

(refer to Figure 

2).

 

Note:

 

Avoid tight radius bends and route the conductor such that it intersects with the VGR in 

a downward manner as illustrated in Figure 1.

 

 

 

 

 

For additional assistance or if you have any questions regarding this notification, please contact 
Alpha Technical Support at 1-888-462-7487 o

www.alpha.ca/report-a-problem. 

 
Sincerely, 
 
Satheesh Hariharan 

 

 

David Veraguth 

Sr. Product Manager, Outside Plant Solutions   

Sr. Technical Support Representative 

Alpha Technologies Ltd. 

 

 

Alpha Technologies Ltd. 

Satheesh.Hariharan@alpha.ca

 

 

 

David.Veraguth@alpha.ca

 

 

 

For assistance, contact Alpha Technical Support: 
Toll Free North America: 1-888-462-7487  
International: +1-604-436-5547  
Monday - Friday, 7:00 AM - 5:00 PM PST for regular inquires 
24/7 for emergency support  

Figure 2 

 TE33-1820 RPN Enclosure Master Ground Bar Wiring 

 