OIL BURNERS MAINTENANCE 
INSTRUCTIONS 

General information

Keep the boiler room clean. Ensure that the boiler 

room has permanent fresh air intake. Switch off before 

dismantling the oil burner.

At hinged mounting, make sure that an automatic safety 

switch is fi tted, so that the burner cannot start when 

theswing door is open.

Don´t use the oil fi red boiler to burn paper or 

rubbish,unless the boiler is especially fi tted with a hinged 

door tomake this possible.

Don´t fi ll tank while burner is working.

Starting precautions

Make sure that the oil tank is not empty

Make sure that the valves on oil and water supply pipes 

areopen.

Make sure that the boiler fl ue damper is open.

Make sure that the boiler thermostat is set at the correct 

temperature.

Switch on the current. Most relay systems have a 

delayed action so that the burner will not start for 

perhaps 20 seconds.

With heavy oil the delay will be longer as the burner 

will notstart until the oil in the preheater reaches the 

requiredtemperature.

If the burner will not start

Press the reset button on the relay. Check that the 

thermostats are correctly adjusted.

Don´t forget the room thermostat, check that any 

fusesare intact and main switch is on. 

If the burner starts but does not ignite

Make an attempt to start the burner.

Never make close repeated start attempts.

Don´t restart the burner until the boiler is free from oil 

gases.

If the burner still does not ignite send for the service 

engineer.

When switching off during summer

Always use the main switch to cut out the burner even 

when adjusting the burner or cutting off the heating for 

ashort time. For longer periods of shut down, close all 

valves and the oil supply stop-cock.

Clean the fi lter and nozzle by washing in petrol or 

paraffi n.

Make sure the fi lter medium is not damaged or defective.

Protect electrical gear from damp.

Warning

Never stand too near or put your face to the inspection 

or fi re door, when the burner is about to start.

Never use a naked fl ame to ignite oil if the electrical 

ignition fails.

Always wait for about 10 minutes for the unburnt gases 

to disperse before restarting the oil burner if it has failed 

to ignite previously.

Installed by: 

Tel:

170 025 01  2012-04-16

10.  OIL BURNERS MAINTENANCE 

INSTUCTIONS

Summary of Contents for Bentone B1FUV Classic

Page 1: ...Providing sustainable energy solutions worldwide 178 066 31 3 2017 10 09 Installation and maintenance instruction B1FUV CLASSIC...

Page 2: ...______________8 5 1 Suspension of burner ____________________________________ 8 5 2 Removing the blast tube__________________________________ 8 5 3 Shrouded disc ______________________________________...

Page 3: ...stor 4 Test nipple fan pressure 5 Frame 6 Blast tube 7 Control box 8 Electric contact X1 X2 see wiring diagram 9 Ignition transformer 10 Oil pump 11 Motor 12 Air adjustment 13 Adjustment of nozzle ass...

Page 4: ...oil ire or personal injury is avoided Care should be taken by the installer to ensure that no electrical cables or fuel gas pipes are trapped or damaged during installation or service maintenance Cond...

Page 5: ...0 bar 11 bar 12 bar Gph kg h kW kg h kW kg h kW kg h kW kg h kW 0 40 1 15 13 6 1 22 14 4 1 28 15 2 1 35 16 0 1 41 16 7 0 45 1 35 16 0 1 43 17 0 1 51 17 9 1 58 18 8 1 65 19 6 0 50 1 57 18 6 1 67 19 8 1...

Page 6: ...ain power switch must be turned off before beginning the electrical installation If the boiler has a 7 pole contact device type Eurostecker it will most often it the burner direct Otherwise use the ac...

Page 7: ...25 30 35 40 45 0 45gph 0 50gph 0 55gph 0 60gph 0 65gph 0 75gph 0 85gph Pump pressure bar Burner capacity kW Nozzle assembly scale 0 2 4 6 8 10 12 14 15 20 25 30 35 40 45 Suction plate 4 Suction plate...

Page 8: ...s one turn 2 Turn to the right and withdraw the blast tube Shrouded disc The preheater plug and the electrodes shall be placed on either side of the oil tube The hole in the shrouded disc shall be pla...

Page 9: ...f the burner If the spark hits the metal the eficiency will be lower and will also cause radio disturbance There is also a risk that carbonisation will occur Since the electrode pack is of the factory...

Page 10: ...nd air according to the recommendations in section Basic set tings For the individual boiler installation adjustments can then always be made to optimise economy operational reliability and environmen...

Page 11: ...from the stud bolt Pull the electric package backwards and rotate it ca 90 clockwise When required the electric package can be suspended in the cables Pump lter When changing pump ilter see chapter 0...

Page 12: ...a one pipe system In two pipe systems the pump is automatically vented by the return pipe Changing cartridge lter Unscrew the ilter screw from the cover using a 4 mm Allen key and pull out the ilter...

Page 13: ...set on the control valve P1 and by the size of the oil nozzle in the nozzle line The control valve P1 operates as follows When the oil attains opening pressure the port to the return side opens The d...

Page 14: ...dividual resistances is negligible The tables do not include any lengths exceeding 100 m because experience shows that longer lengths are not needed The tables apply to standard fuel oil of normal com...

Page 15: ...in switch T1 Ignition transformer Y1 Solenoid valve X1 Plug in contact burner X2 Plug in contact boiler The colours of the preheater cable A Blue B Brown C Black Outer electrical connection Mains conn...

Page 16: ...t 3 4 Operating position If the burner operation is interrupted by means of the main switch or the thermostat a new start takes place when the conditions in accordance with point 1 are fulilled The oi...

Page 17: ...caused the problem by pressing and holding the reset button for 3 seconds The number of lashes below is repeated with a pause in between 2 lashes No lame signal when safety time expires 4 lashes Fals...

Page 18: ...r runs to lockout Fuse has blown Appliance thermostat has not reset Appliance overheat device has operated Control relay or photocell defective No oil being delivered Excessive lue draught is preventi...

Page 19: ...19 9 DECLARATION OF CONFORMITY...

Page 20: ...t start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If the burner starts...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Reviews: