HANDING OVER OF THE INSTALLATION

172 305 17  93-01

-

Make repeated start attempts to
ensure that the adjustments func-
tion.

-

Close the ball valve during opera-
tion to check that the gas switch
switches off at the set value.

-

Remove the hose for the air pressu-
re switch to check that the burner
locks out.

-

Check that all protective covers
and measurement nipples are
mounted and fastened.

-

Fill out necessary test reports.

-

Instruct the persons in charge of the
operation on the service  and main-
tenance of the installation and what
to do should any troubles occur.

-

Inspection and service must only
be  carried  out  by  authorized
people.

FAULT LOCATION, FUNCTIONAL
TROUBLES

Trouble free operation is dependent on
three factors: electricity, gas and air
supply. Should there be any changes
in the ratio between these three factors
there is a risk of break downs. It has
been proved that most break downs are
caused by simple faults. Before calling
the service engineer, the following
should therefore be checked:

-

Is the gas cock open?

-

Are all fuses in order and the cur-
rent switched on?

-

Are the thermostats correctly set?

-

Are pressostats, overheating pro-
tection etc. in operating position
and not locked-out?

-

Is the gas pressure sufficient?

-

Is the gas burner control in start
position?

-

Has the gas control or the motor
protector locked out? - Reset.

-

Is the circulation pump in opera-
tion?

-

Is there a supply of fresh air to the
installation?

If integral components are of a diffe-
rent make from what is stated in this
manual, see the enclosed loose-leaf.

Summary of Contents for Bentone BG 450

Page 1: ...Providing sustainable energy solutions worldwide 178 011 75 2 2016 11 28 Installation and maintenance instruction BG 450...

Page 2: ......

Page 3: ...ide stop is installed before servicing Take great care when servicing Trap and pinch risks can be present The boiler s sound level can exceed 85 dBA during operation Use ear protectors when present in...

Page 4: ...10 Motor 18 Switch l ll Formodulatingburner Change overswitchmanually automatically 19 Indicating lamp Stage 1 20 Switch 0 1 21 Contactor 22 Controlbox 23 Ignitiontransformer 24 MultiBloc 11 Connecti...

Page 5: ...G Naturalgas LPG Naturalgas LPG 450 120 550 12 4 6 55 21 360 40 30 50 2 Town gas 2 Town gas 2 Town gas 2 Town gas OUTRANGE TECHNICAL DATA Type designation BG 450 DIMENSIONS 1 Calorificvalue Natural ga...

Page 6: ...TECHNICAL DATA DIMENSIONSOFFLANGE 172 215 19 00 01 14 210 254 280 163...

Page 7: ...itch maxi 6a Mainvalve 7 1 2 3 5a 5b 4 6b 6a 10 Incorporated in the MultiBloc 9 6b Safetyvalve 1 7 Valveprovingsystem 9 Air pressure switch 10 Gasburnercontrol Pos 5b 7 Components not required accordi...

Page 8: ...very useful DO LIKE THIS Remove the cover of the fan hous ing LoosenthenutDofthegasassem bly package Loosen ignition cable and ionisa tion cable of gas assembly Loosen the screw A on both sides Pull o...

Page 9: ...1 5x max inlet pressure or min 150 mbar If any leakage locate the source by means of soapy water or a leak location spray After tightening repeat the test ELECTRICFUNCTIONTEST Ensurethatphaseandneutr...

Page 10: ...MEASURES AND CHECKS BEFORE START UP INNER ASSEMBLY Town gas INNER ASSEMBLY Natural gas LPG INNER ASSEMBLY Biogas UV detector 172 205 18 97 01 Propan Naturgas...

Page 11: ...essure of the gas at the gas meter 15 0 mbar f f 1 11 The gas volume read on the gas meter actually reads 1 11 12 9 14 4 m3 h Net calorific value Gasquality kWh Nm3 kJ Nm3 kcal Nm3 Naturalgas 10 3 37...

Page 12: ...perating switch S3 Control thermostat S4 Temperature limiter S5 Micro switch for hinged door S7 Main switch S8 Air pressure swith S9 Gas pressure switch T1 Ignition transformer X1 Connection terminal...

Page 13: ...ration LME 11 permits a maximum of three start attempts if the start cycle is uninterrupted Continuous Off Red Yellow Green Colour code table for multi coloured signal lamps Light diodes Status Colour...

Page 14: ...ressing the reset button 0 5 3 s Connecting signal ampliier Alarm control table Red lashing code on signal lamp LED Possible causes Flashing 2 x No lame at End of TSA Defective or obscured lame monito...

Page 15: ...Theflowadjustmentcanalsobemade by means of the governor Adjust the outlet pressure to a value giving the desired gas flow on the fully open valve Atsmallcapacities gasflows it is also necessary to ad...

Page 16: ...the sections dealing with adjustments of multi bloc com bustion air and combustion head Open the ball valve and switch on the main switch If the burner starts the actual adjustment can be made ADJUSTM...

Page 17: ...ichthegasswitchshouldswitchoff Set this pressure by means of the valve Carefully turn the knob see figure until the gas pressure switch switches off The value shown on the scale should then approximat...

Page 18: ...Troublefreeoperationisdependenton three factors electricity gas and air supply Should there be any changes intheratiobetweenthesethreefactors there is a risk of break downs It has beenprovedthatmostbr...

Page 19: ...cient 5 Is the gas relay of the burner ready for start and not lockedout 6 Is the air supply to the burner sufficient To facilitate fault location we have drawn up a scheme showing the most frequent f...

Page 20: ...on the secondary side The ignition cable and the ionisation cable have been transposed Noflameestablishmentinspiteofatroublefreestart Thegassolenoidvalvedefective The gas solenoid valve does not open...

Page 21: ...cell is in a wrong position Voltage drop at certain times Air pressure switch defective or incorrectly adjusted Spark over in ignition electrodes REMEDY Contact the electricity authorities Adjusttheig...

Page 22: ...ply Insulate the chimney CAUSE The ambient temperature of the gas relay is too high The ignition spark is too weak Badcombustion Bad draught conditions The flue gas temperature is too high The CO2 con...

Page 23: ...le marquage CE de conformit Ljungby Sweden 141127 27 11 14 ENERTECH AB Bentone Division Box 309 SE 341 26 Ljungby Sweden H kan Lennartsson Enertech AB declares that the above mentioned products compl...

Page 24: ...ample room ther mostat if any 4 Check that the gas pressure to the burner is sufficient 5 Check that the electric fuses have not blown 6 Make a new attempt to start the burner and check the counter of...

Page 25: ...Measure ment Before After C A mbar mbar Small flame Large flame Measures Date Nm3 gas h Governor CO2 CO Flue gas temp Ionisa tion current Pressure Efficiency Fire room Chimney Measure ment Before Aft...

Page 26: ......

Page 27: ......

Page 28: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...

Reviews: