4. Basic settings
4.1 Example of basic settings
4.1.1 Choice of nozzle
ST 120 R 69-16
Burner output
30 kW
Estimated nozzle output:
30 / 11.86*
=
2.53 kg/h
Choice of nozzle according to the table (refer to Technical data).
According to the nozzle table, this provides the following nozzle.
Nozzle:
0.65 GPH
Pump pressure:
11.0 bar
ST 120 R 69-16 /ST 120 RV 69-16
Burner output
30 kW
Output calculation due to preheater for nozzle choice according to the table
(refer to Technical data).
Estimated nozzle output:
30 x 1.06
=
31.8 kW
31.8/11.86 *
=
2.68 kg/h
Choice of nozzle according to the table (refer to Technical data).
According to the nozzle table, this results in the following nozzle.
Nozzle:
0.75 GPH
Pump pressure:
9.5 bar
1.1.1
Basic settings
The setting value for 30 kW according to basic settings tables
(Setting values).
Air setting
=
11.0
Insert setting
=
4.0
* Energy value of EO1 fuel oil = 11.86 kWh/kg