40
CTC EcoLogic Pro/Family
For the property owner
Prio. EcoAir/EcoPart
°
C
7 (-20 to 15)
This temperature setting controls the prioritisation
between the EcoAir air/water heat pump and the
EcoPart liquid/water heat pump, if both of these are
connected to EcoLogic. The factory value is 7°C;
this means that the EcoAir is prioritised for outside
temperatures from 7°C and warmer.
Charge pump %
50 (20...100)
The charge pump’s speed can be adjusted. The
temperature through the heat pump can be read in
“Operation data/ operation data compressor”.
Only valid for heat pump CTC EcoAir 500M.
Select/Rename Heat pump
(A1/A2/A3)
When CTC EcoZenith i550 is to control more than one
heat pump, the names of heat pumps 2 and 3 must be
changed. On delivery, the heat pumps are set to A1.
For more information, see the manuals for
CTC EcoAir 520M/510 230V 1N~
CTC EcoPart 400 and CTC EcoAir 400 name is
changed with CTC Basic Display
NB: Only valid for heat pump CTC EcoAir 500M
Cont. brine pump on
No (No/Yes)
Setting for whether the brine pump is permitted to run
all the time or permitted to start and stop.
Applies to EcoPart heat pumps only.
Compressor stop at brine °C
-5 (-7 to 10)
This menu deines the brine temperature at which the
compressor will be stopped.
Applies to EcoPart heat pumps only.
Brine pump on 10 days
Off (Off/On)
After installation is complete, you can choose to run the
brine pump constantly for 10 days to remove air from
the system.
Applies to EcoPart heat pumps only.
Tariff HP
No (No/Yes)
Find out more in section entitled “Deine/Remote
control”.
Smart block HP
No (No/Yes)
This is used when a dual tariff is used with lower energy
costs at set hours of the day. Find out more in section
entitled Deine/Remote control/Smart Grid
EP
System
Heat-
pump
EA
EA(M)
1 2 3 4 5 6
1
EP
System
Heat-
pump
EA
EA(M) 1
2
3
4
5
6
1-10
EP
System
Heat-
pump
1
2
3
4
5
6
1-10
System
Heat-
pump
EA(M) 1
2
3
4
5
6
1-10
Summary of Contents for CTC EcoLogic Family series
Page 2: ......
Page 3: ...162 105 48 3 2016 04 08 Installation and Maintenance Manual CTC EcoLogic Pro Family...
Page 67: ...67 CTC EcoLogic Pro Family For the property owner...
Page 120: ...120 CTC EcoLogic Pro Family For the installer 11 Wiring diagram...
Page 121: ...121 CTC EcoLogic Pro Family For the installer...
Page 127: ......