98
CTC EcoLogic Pro/Family
For the installer
9.3.1
CTC EcoLogic systems 4 and 5 – Heating
circuit
The CTC EcoLogic can be connected to four different heating circuits, each
with separate room sensors. Heating circuits 1 to 4 are connected via mixing
valves (Y1, Y2, Y3 and Y4).
For EcoLogic system 4, if additional heat (E1) is deined, the mixing valve
(Y2) should be used to connect additional heat to the system (not to heating
circuit 2).
The outdoor sensor (B15) must be itted to the outer wall of the house,
protected from direct sunlight. It is connected using a 2-conductor cable
(min. 0.5 mm²).
The room sensors (B11 to B14) must be itted in an open space in the
property where a representative temperature is expected. They are
connected using a 3-conductor cable (min. 0.5 mm²).
The primary low sensors (B1 to B4) must be placed on the primary low of
the respective heating circuit.
The sensor (B7) is placed on the return low from the heating circuit.
Heating circuit 4
Heating circuit 3
Heating circuit 2
Heating circuit 1
Pool
Buffer tank