Installation instructions for professionals
169
Temperature shown
on front of panel
Outside air
temperature
The alternatives are outside air temperature, supply
air temperature and extract air temperature.
5
Use
Home
The options are Home or Office. In the Office mode,
the unit can be switched on only by using a timer.
Temperature control Supply air
Extract air is the
default setting for
units with cooling
functionality.
Supply air is not allowed in Pallas HP units
.
Room temperature average
or
Extract air c
ompare the
temperature setting in the main view with the room
temperature or extract air temperature and heat or
cool the supply air accordingly. To be able to use
room temperature control
, at least one room tempe-
rature sensor must be
connected.
Extract air
is the default setting for units with cooling
functionality.
Cooling
Options are ON/OFF.
Outside temperature
limit for cooling
17°C
When the outside temperature is below the set value,
no active cooling is allowed.
Heating
ON
Options are ON/OFF.
Outside temperature
limit for heating
25°C
When the outside temperature is above the set value,
no heating is allowed.
Min. supply air
temperature
13°C
This is the minimum temperature for the supply air
when the temperature control value is
Extract air
or
Room temperature average
.
Maximum supply air
temperature
40°C
This is the maximum temperature for the supply air
when the temperature control value is
Extract air
or
Room temperature average
.
Heating/cooling
limitation
OFF
This setting is used if the user wants to prevent con-
tinuous switching between heating or cooling when
the temperature setpoint is very close to the desired
temperature.
Heating
18°C
When the extract air (or the room temperature ave-
rage, in room temperature mode) temperature drops,
the heating is not activated until this temperature is
reached If heating/cooling limitation is on.
Cooling
24°C
When the extract air (or the room temperature ave-
rage, in room temperature mode) increases, the coo-
ling is not activated until this temperature is reached
if heating/cooling limitation is on.
TE20-21 sensor
OFF
Options are ON/OFF. If both sensors are selected
here, the temperature control uses the mean tempe-
rature of the room sensors. If you have installed only
one wall mounting bracket with room temperature
sensor, it is TE20.
Room temperature
sensor 1-3
OFF
Options are ON/OFF. These sensors are room tempe-
rature transmitters that are connected to the venti-
lation unit. The sensors can be included or left out of
the mean room temperature measuring by setting
them on or off.
Summary of Contents for Pallas eAir EnergyBUS KIW
Page 8: ...8 Kanavaliitännät ulkoilma poistoilma jäteilma tuloilma ...
Page 46: ...46 ...
Page 47: ...47 Ammattilaisen asennusohje ...
Page 48: ...48 Installationsanvisningar för ventilationsaggregat Svenska Pallas HP eAir ...
Page 54: ...54 Kanalanslutningar uteluft frånluft avluft tilluft ...
Page 92: ...92 ...
Page 93: ...Installationsanvisningar för yrkesfolk 93 ...
Page 94: ...94 Installeringsinstruksjoner for ventilasjonsenheten Norsk Pallas HP eAir ...
Page 100: ...100 Kanalanslutningar uteluft avtrekk avkast tilluft ...
Page 138: ...138 ...
Page 139: ...Installasjonsinstrukser for fagfolk 139 ...
Page 140: ...140 Installation instructions for the ventilation unit English Pallas HP eAir ...
Page 146: ...146 Duct connections outdoor air extract air exhaust air supply air ...
Page 183: ...Installation instructions for professionals 183 ...
Page 184: ...184 ...
Page 194: ...194 Koblinger Connections ...
Page 205: ...205 ...