Installation instructions for professionals
171
8
Defrost
OFF
Options are ON/OFF. The function is active during
winter season, if enabled. When defrosting is active,
the rotary heat recovery wheel speed is modulated
at predetermined intervals, according to exhaust air
temperature.
Limit temperature
for winter boost
8°C
When the outside temperature is below this value,
the heat recovery is always on 100%. This setting has
no effect in HP models.
Arctic mode
OFF
Options are ON/OFF. Arctic mode is a defrosting
mode that takes the outside air temperature and
the absolute humidity of the extract air into account
when determining the need for defrosting.
Operating modes
9
Supply air
30 %
This value defines the supply air fan speed in Home
operating mode.
Extract air
30%
This value defines the extract air fan speed in Home
operating mode.
10
Supply air
30%
This is the minimum supply fan speed when heat
pump is running. In Pallas HP units this setting must
be set to allow for a minimum airflow of 200 l/s.
Extract air
30%
This is the minimum extract fan speed when heat
pump is running. In Pallas HP units this setting must
be set to allow for a minimum airflow of 200 l/s.
11
Summer night
cooling
OFF
Options are ON/OFF. Summer night cooling boosts
the fan speed to increase cooling when the outside
air is cooler than the room air.
Summary of Contents for Pallas eAir EnergyBUS KIW
Page 8: ...8 Kanavaliitännät ulkoilma poistoilma jäteilma tuloilma ...
Page 46: ...46 ...
Page 47: ...47 Ammattilaisen asennusohje ...
Page 48: ...48 Installationsanvisningar för ventilationsaggregat Svenska Pallas HP eAir ...
Page 54: ...54 Kanalanslutningar uteluft frånluft avluft tilluft ...
Page 92: ...92 ...
Page 93: ...Installationsanvisningar för yrkesfolk 93 ...
Page 94: ...94 Installeringsinstruksjoner for ventilasjonsenheten Norsk Pallas HP eAir ...
Page 100: ...100 Kanalanslutningar uteluft avtrekk avkast tilluft ...
Page 138: ...138 ...
Page 139: ...Installasjonsinstrukser for fagfolk 139 ...
Page 140: ...140 Installation instructions for the ventilation unit English Pallas HP eAir ...
Page 146: ...146 Duct connections outdoor air extract air exhaust air supply air ...
Page 183: ...Installation instructions for professionals 183 ...
Page 184: ...184 ...
Page 194: ...194 Koblinger Connections ...
Page 205: ...205 ...