161
Installation instructions for professionals
Half-warm space* can mean a lowered ceiling,
midsole, or casing.
NOTE
The duct coils to be installed in the ventilation
system must be insulated in the same way as the
ventilation ducts are. The ceiling mounting plate is
an extra sold separately.
NOTE
Outside air intake duct
(fresh air intake duct)
Cold space:
•
100 mm plate, mat or pipe insulation (+ additional
possible blowing wool).
Warm/semi-warm* space and suspended ceilings,
intermediate floor and enclosures:
•
Option 1: 80 mm insulation with steam-tight surface
•
Option 2: 20 mm cellular rubber insulation on the
surface of the duct and 50 mm insulation on the
steam-tight surface.
Insulation must prevent the condensation of steam on the
outer surface of the duct. In summer it must prevent the
air from heating too much.
Supply air duct
Cold/semi-warm* space and lowered ceilings,
intermediate floor and enclosures:
•
In basic ventilation, the insulation must be planned
and implemented so that changes in the temperature
of airflow are less than 1°C. It is possible to use 100
mm plate, mat or pipe insulation, for example (as well
as possible blowing wool).
Warm space:
•
Basic ventilation does not require insulation.
For heating and cooling uses, cf. tables “Insulating
ventilation ducts for heating” and “Insulating ventilation
ducts for cooling”.
Examples of ventilation duct insulation
Soundproofing is not included in these insulation
instructions and examples.
Exhaust air duct
Warm space:
•
Basic ventilation does not require insulation.
Cold/semi-warm* space:
•
In basic ventilation, the insulation must be planned
and implemented so that changes in the temperature
of airflow are less than 1°C. It is possible to use 100
mm plate, mat or pipe insulation, for example (as well
as possible blowing wool).
If used for heating or cooling, cf. tables “Insulating
ventilation ducts for heating” and “Insulating ventilation
ducts for cooling”.
Extract air duct
Cold space:
•
100 mm plate, mat or pipe insulation
Warm/semi-warm* space:
•
Option 1: 80 mm insulation with steam-tight surface
•
Option 2: 20 mm cellular rubber insulation on the
surface of the duct and 50 mm insulation on the
steam-tight surface.
Insulation must prevent the condensation of steam on the
inner and outer surface.
* semi-warm space = +5... +15°C
Summary of Contents for Pelican eAir
Page 8: ...8 Kanavaliitännät ulkoilma poistoilma jäteilma tuloilma ...
Page 20: ...20 13 15 11 14 Lisävaruste 1 2 min 12 9 10 ...
Page 49: ...49 Ammattilaisen asennusohje ...
Page 52: ...52 Pelican eAir Installationsanvisningar för ventilationsaggregat Svenska ...
Page 58: ...58 Kanalanslutningar uteluft frånluft avluft tilluft ...
Page 70: ...70 13 15 11 14 Extra tillbehör 1 2 min 12 9 10 ...
Page 99: ...99 Installationsanvisningar för yrkesfolk ...
Page 102: ...102 Installeringsinstruksjoner for ventilasjonsenheten Norsk Pelican eAir ...
Page 108: ...108 Kanalanslutningar uteluft avtrekksluft avkastluft tilluft ...
Page 120: ...120 13 15 11 14 Ekstrautstyr 1 2 min 12 9 10 ...
Page 149: ...149 Installasjonsinstrukser for fagfolk ...
Page 152: ...152 Pelican eAir Installation instructions for the ventilation unit English ...
Page 158: ...158 Duct connections outdoor air extract air exhaust air supply air ...
Page 170: ...170 13 15 11 14 Extra 1 2 min 12 9 10 ...
Page 199: ...199 Installation instructions for professionals ...
Page 205: ...205 ...
Page 206: ...206 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...
Page 207: ...207 ...
Page 211: ...211 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...
Page 220: ...220 eAir CG liitännät eAir CG anslutningar eAir CG koblinger eAir CG connections ...
Page 223: ...223 ...