180
Boost functions
14
% RH boost
OFF
Options are ON/OFF. This setting allows or prohibits
boosting according to the air humidity.
Summaer / winter
limit temperature
4°C
When the 24 hour mean temperature of outside
air is higher than this limit, boosted ventilation
based on the 48 hour mean humidity of extract air
is taken into use. If the 24 hour mean temperature
is below the value set here, a fixed limit for boosted
ventilation is used.
% RH boost limit
value
45 %
In winter mode (24 h mean temperature of outside
air is less than +4°C) boosted ventilation activates
when relative humidity is higher than this value.
Threshold value 48
hr % RH
15 %
In summer mode (24 h mean temperature of out-
side air is higher than +4°C) boosted ventilation
activates when relative humidity of extract air is
higher than the 48 h mean humidity by the value
set here.
Max. supply air fan
speed
90 %
The maximum allowed speed of the supply air fan
during boosted humidity ventilation.
Max. extract air fan
speed
90 %
The maximum allowed speed of the extract air fan
during boosted humidity ventilation.
Rotor
dehumidification
OFF
Options are ON/OFF. If allowed rotor dehumidifica-
tion is active when humidity boosting is active and
the outside air temperature is below 0 °C.
15
CO2 boost
OFF
Options are ON/OFF. This setting allows boosting of
the fans according to the CO2 level. CO2 settings
require an external carbon dioxide transmitter (not
included in the basic delivery).
CO2 boost limit
value
1000 ppm
Boosting starts when the amount of CO2 exceeds
the value set here.
Max. supply air fan
speed
90%
The maximum allowed speed of the supply air fan
during boosted CO2 ventilation.
Max. extract air fan
speed
90%
The maximum allowed speed of the extract air fan
during boosted CO2 ventilation.
Summary of Contents for Salla eAir
Page 20: ...20 9 13 15 11 10 14 Lisävaruste 1 2 min 12 ...
Page 46: ...46 ...
Page 49: ...49 Installationsanvisningar för yrkesfolk ...
Page 50: ...50 Salla eAir Installationsanvisningar för ventilationsaggregat Svenska ...
Page 68: ...68 9 13 15 11 10 14 Extra tillbehör 1 2 min 12 ...
Page 94: ...94 ...
Page 97: ...97 Installasjonsinstrukser for fagfolk ...
Page 98: ...98 Installeringsinstruksjoner for ventilasjonsenheten Norsk Salla eAir ...
Page 116: ...116 9 13 15 11 10 14 Ekstrautstyr 1 2 min 12 ...
Page 142: ...142 ...
Page 145: ...145 Installation instructions for professionals ...
Page 146: ...146 Salla eAir Installation instructions for the ventilation unit English ...
Page 164: ...164 9 13 15 11 10 14 Extra 1 2 min 12 ...
Page 190: ...190 ...
Page 193: ...193 ...
Page 200: ...200 ...
Page 201: ...201 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...
Page 202: ...202 ...
Page 206: ...206 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...
Page 207: ...207 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...