Programming the Egress Delay/Warning:
With most keypads, the egress button provides a simple way for someone inside a protected
premises to exit through a locked door by pressing a button instead of using a keypad. However,
in some situations, delaying the egress operation and/or providing some warning when the egress
button is used is desirable.
For example, in hospitals or schools, it may be desirable to delay the egress operation and provide
a warning to prevent patients or young children from easily leaving the protected area.
For simple egress with no delay or warning, do not change this setting. It is disabled by default.
When programming the egress delay/warning, use this general formula:
90 a bb #
90
– Program Egress Delay/Warning
A
– Egress Mode
BB
– Delay Time
Egress Modes:
There are four possible egress operation configurations for the keypad:
•
1
Momentary contact with no warning (default) – Press the egress button momentarily. The
door opens instantly (default) or after the programmed delay time with no audible warning.
•
2
Momentary contact with warning beep – Press the egress button momentarily. The keypad
will beep for the programmed delay time before letting the door open, to warn that someone is
preparing to exit the protected area.
•
4
Hold contact with no warning – Press and hold the egress button for the programmed delay
time until the door is open. This prevents accidental opening of the door.
•
5
Hold contact with warning beep – Press and hold the egress button for the programmed
delay time until the door is open. The keypad will beep during the delay time before letting the
door open, to warn that someone is preparing to exit the protected area.
NOTE: When the egress button is programmed to hold for a delay time before the door is
released, it is important to put a sign near the egress button to notify users of the
delay time.
Delay Time:
•
0
– No delay time (default): Output #1 operates immediately when the egress button is
pressed.
•
1
to
99
– Egress button delay time: The delay time can be set from 1 to 99 seconds. This
tells the keypad how long to wait after the egress button is pressed before activating output #1.