CenCon
33
Once the above values have been confirmed and
set, again press
High fire
button and allow O
2
levels to stabilize. Press
Low Fire
, and release the
High fire
button. As the burner reduces to low fire,
observe O
2
levels to ensure they do not drop below
the high fire
O
2
setting by more than 0.3. If this
occurs there is air fuel curve error and must be
reset with the above steps.
Press:
Setup Complete.
Press to disable
Service Mode.
Return to the home screen by pressing the
Left
arrow key, and then press Save User Settings.
Combustion setup is now complete.
m
NOTICE:
The
Tracking Okay
light indicates the stroke time
of the actuators are in sync, within 5%. If not
illuminated, one actuator is waiting for the other to
catch up.