CenCon
41
LP2
AI
Low pressure
sensor #2
Analog suction pressure transducer, circuit #2.
0-10 Vdc
LP3
AI
Low pressure
sensor #3
Analog suction pressure transducer, circuit #3.
0-10 Vdc
LP4
AI
Low pressure
sensor #4
Analog suction pressure transducer, circuit #4.
0-10 Vdc
LP5
AI
Low pressure
sensor #5
Analog suction pressure transducer, circuit #5.
0-10 Vdc
+5V
+5 Vdc
DC +5 power source
5 Vdc
GC
DC common
DC common
DS+-
AI
Dehumidify
Setpoint
0-100%RH Setpoint for dehumidification operation.
0-10 Vdc
EnH
DI
Enable reheat
Enable / disable hot gas reheat.
24 Vac
EnC
DI
Enable cooling
Enable / disable mechanical cooling.
24 Vac
CW1,2
AI
Chilled Water
sensor
10k Type 2 thermistor
Ohms (Ω)
STAGED COMPRESSORS
On a call for cooling, the compressors will stage on from 1 to 6. The CenCon cooling programming does not
allow for random start, only sequential. Inter-stage and anti-cycle timing is built into the CenCon program and
is not adjustable.
On the initial call for cooling only, the inter-stage time of the first 2 stages is decreased.
AMBIENT CONDENSER FANS
The CenCon may incorporate up to 2 ambient temperature based condenser fan (or ambient based
compressors) enable contacts.
LOW AMBIENT LOCKOUT
Mechanical cooling is disabled below the design low ambient lockout setpoint, typically set at 50°F (10°C), and
58°F (14°C) for makeup air appliances.