CenCon
48
TERMINAL DESCRIPTION
Terminal
Type
Name
Description
Value
H N
Power Supply
24 Vac
GND
Ground
Connect to chassis.
LmA B
Modbus
Internal Network
MFr
AO
Modulating
Bypass Damper
Demand
Modulating output to bypass damper actuator.
0-10 Vdc
MER
AO
Drive Motor
Speed Signal
Modulating output to heat wheel drive motor, heat pipe
tilt actuator, or heat plate damper actuator.
0-10 Vdc
EnH
DI
Enable energy
recovery
Enable energy recovery operation.
24 Vac
Rot
DI
High Speed
Enable
Input from rotation sensor.
24 Vac
CM / ByD
DO
Bypass Damper Dry contact enable bypass damper.
24/120 Vac
CM / ERC
DO
Relay Common
Dry contact enable wheel motor starter.
24/120 Vac
LA1,2
AI
Leaving
(Supply) Air
Temperature
10k Type 2 thermistor
Ohms (Ω)
EA1,2
AI
Exhaust Air
Temperature
10k Type 2 thermistor
Ohms (Ω)
ALARM DESCRIPTION
Sensor Failure
Exhaust or Leaving wheel sensor open or shorted.
Defrost Active
Temperatures approaching frost temperature. Control signal reduces.