CenCon
58
Combustion Record - DJ
m
High fire gas and air offsets should be set to zero. Use the PacMan to set air and the
appliance regulator to set gas.
Serial and Tag#
Date
Model #
Technician
Job Name
Location
Sequence
1
2
3
4
5
6
Name
High Fire
Near High
Fire
Low Fire
Near Low
Fire
Medium
Fire 1
Medium
Fire 2
% Fire
100
90
6.67
10
25
55
Man. Press.
Oxygen - O
2
CO
RPM
Air Offset
0
Gas Offset
0
*
Gas mA/Vdc
FACTORY CLOCKING
Clocking
Calculated
Clock Ratio
1.0
1.1
15.0
10.0
4.0
1.8
* Set to zero when using Maxitrol. Low fire is set on valve mechanical bypass. Only adjust offset if
unable to achieve clocking with the bypass.
Setup Comments: