A
CRD-200
11 of 14
Sep 06
PAGE 10 – SAVE SETPOINTS
1 0 S A V E S E T P O I N T S
< ? >
-Location to save any setpoint changes made to the C-TRAC3 into permanent flash memory.
PAGE 11 – UNIT ON/OFF
1 1 U N I T O N / O F F
< O N
>
-If enabled, this page will allow the user to enable or disable equipment operation.
PAGE 12 – LOW LIMIT
1 2 L O W L I M I T O K
< S E T P T = 4 0
o
F >
-The low limit, or freeze protection, setpoint is preprogrammed and cannot be changed from
the CRD-200.
-This page indicates the low limit setpoint and alarm indication.
PAGE 13 – SENSOR FAILURE
1 3 T E M P S E N S O R S O
K
< >
-If any of the 2 or 3 sensors used by the C-TRAC3 exceed the predetermined resistance
range, and alarm is indicated.
PAGE 14 – HEAT ALARMS
1 4 H E A T A L A R M
< F L A M E F A I L >
-Used to provide feedback regarding gas-fired and electric heating operational issues.