CRD-200
9 of 14
Sep 06
PAGE 1 – UNIT OPERATION
E n g A F A N D E L A Y O N
< # 0 1 H T G M O D E >
-Describes the current operating mode and fan status, as well as the program number.
PAGE 2 – DISCHARGE AIR
2 D I S A I R =
6 5
o
F
< A D J S E T P T = 7 0 >
-Notes the discharge air temperature and setpoint. Multizone equipment will indicate the hot
deck temperature. Dehumidification equipment will refer to the final reheat temperature.
-Setpoint changes can be made here, but will not be saved unless saved to flash memory.
PAGE 3 - HEATING
3 H T G = 8 7 %
< M A I N H E A T O N >
-Shows the actual heating signal output (%) from the C-TRAC3 to the heating device.
-Indicates the return signal to confirm heating is operational.
PAGE 4 - COOLING
4 C L G = 3 3 %
< C Y C L I N G O N >
-Describes the number of cooling stages as a percentage. For example, if the equipment has
3 compressors the output will indicate 33, 66 and 100%.
-Also indicates any control corrections in progress.
PAGE 5 - ECONOMIZER
5 E C O N = 7 0 %
< A D J M I N P O S = 1 0 % >
-Indicates the actual C-TRAC3 economizer output and the minimum outside air setpoint (%).
-Setpoint changes can be made here, but will not be saved unless saved to flash memory
(page 10).
-Deviations may occur between setpoint and actual output. Refer to the
C-TRAC3 manual for clarification.