background image

April 23, 1999

Page 9

IMPORTANT:THE EXHAUST CAP MUST BE A MINIMUM OF 24" OR 6" ABOVE THE 

EXPECTED SNOW DEPTH ON THE ROOF, WHICH EVER IS GREATER, ONCE 
THE INSTALLATION IS COMPLETE.  VERTICAL PIPE EXTENSIONS OVER 
12" MUST BE INSULATED BY A SUITABLE METHOD.

3. Insert the thimble through the roof and secure in place using the mounting bracket or a 

suitable support.

4. Install the flue pipe through the thimble ensuring that the minimum clearance accounting for

snow depth is observed.  Secure the flue pipe to the inner pipe of the thimble with corrosion
resistant screws and high temperature sealant.  The joint between the thimble and flue pipe
must be sealed, and the flue pipe must be flashed to the roof.   Attach the exhaust cap to the
end of the flue pipe and secure with 2 corrosion resistant screws and high temperature
sealant.

5. Install flue pipe between the vent terminal and the Heater.  All pipe joints must be sealed with

high temperature tape and silicone sealant, and secured with corrosion resistant sheet metal
screws.  High temperature tape shall be wrapped two full turns around each joint.  Ensure the
flue pipe is adequately supported for vertical venting as per CAN1-B149 codes latest
addition.

C. OPTIONAL VERTICAL VENT TERMINAL

Your power vented Heater may be vented using an existing Type B vent terminal provided the
following conditions are met.

1. Ensure the installation meets local venting codes and CAN1-B149 codes latest edition.
2. Size vent pipe from an approved vent table using Fan Max Column.  (Tables may be found

in CAN1-B149 codes).

3. Ensure that the only large diameter vent pipe is the vent terminal itself, i.e. the expansion

must take place at the vent terminal.

4. Ensure the vent terminal is in good condition, clean, and gas tight.  If there is damage or if

the vent terminal is corroded, a   vent terminal as described early is recommended.

5. Install flue pipe between the existing vent terminal and the Heater.  All pipe joints must be

sealed with high temperature tape and silicone sealant and secured with corrosion resistant
sheet metal screws.  WE RECOMMEND USING 3M TYPE 433 OR 363 ALUMINUM TAPE. 
High temperature tape shall be wrapped two full turns around each joint.  Ensure the flue
pipe is adequately supported for vertical venting as per CAN1-B149 codes, latest addition.

RECOMMENDED METHOD OF INSULATING THE SINGLE WALL VENT PIPE  (A 6" clearance
to combustible material must be maintained).

1. It is required that any vent connector pipe which runs through unheated space be insulated

with 1" fibreglass insulation as described in FIGURE # 4 and FIGURE # 5.  In heated space it
is acceptable to omit insulation.

2. After the vent pipe has been properly sealed and properly supported, the one piece pipe

insulation may be installed.

3. First insulate all the straight sections of vent pipe but do not fasten.
4. Vent pipe elbows may be insulated by miter cutting a straight section of one piece pipe

insulation.

5. Once the entire length of vent pipe has been enveloped, peel off the release paper and seal

all joints.  Seal by pressure with hands working from the centre out.  (See figure 4).

6. Remove the release paper from the butt strips and wrap snugly around butt joints.  (See

figure 5).

Summary of Contents for DH-FP-PV series

Page 1: ...RETAIN INSTRUCTIONS WITH UNITAND MAINTAIN INALEGIBLE CONDITION PLEASE GIVE MODEL NO SERIAL NO WHEN CONTACTING FACTORY FOR INFORMATIONAND OR PARTS FORM PV 8 99 INDOOR POWER VENTED INDIRECT GAS FIRED HE...

Page 2: ...WALL INDIVIDUAL VENT 6 B VERTICAL INDIVIDUAL VENT 8 C OPTIONAL VERTICAL VENT TERMINAL 9 INSULATION OF SINGLE WALL VENT PIPE 9 COMBUSTION AIR 10 GAS INSTALLATION 10 DUCTWORK 11 ELECTRICAL INSTALLATION...

Page 3: ...l ENGINEERED AIR s obligations with respect to this warranty The refrigerant charge is not included in any part of this warranty ENGINEERED AIR shall not be liable to any damage to person or property...

Page 4: ...cial and Local Codes In USA a All gas piping must be installed in accordance with the National Fuel Gas Code ANSI Z223 1 latest edition The local authority having jurisdiction should be consulted for...

Page 5: ...units 1 HB HIGH BOY UNITS a Place heat section on top of fan section so the heat section is 1 2 13 behind the fan section b Carefully slide the heat section forward until the back and sides of the he...

Page 6: ...ed to locate the screws c The unit is now one piece locked together by four sheet metal screws d Pull wires from the motor wire way tube into the fan compartment and connect these wires to motor accor...

Page 7: ...ed 25 The minimum length of vent pipe is 6 One 6 diameter 90 degree elbow is equivalent to four feet of straight pipe Be sure to consider all elbows when planning the vent G All connections between th...

Page 8: ...required for clearance to combustibles 2 Prepare the lengths of flue pipe to be used Be sure to account for the position of the mounting brackets and wall thickness The flue pipe must extend beyond t...

Page 9: ...ter regulator assembly within 3 feet 1m horizontally of the vertical centre line of the regulator iv within 6 feet 1 8 of any gas service regulator vent outlet See Figure 3 for minimum clearances Size...

Page 10: ...Fan Max Column Tables may be found in CAN1 B149 codes 3 Ensure that the only large diameter vent pipe is the vent terminal itself i e the expansion must take place at the vent terminal 4 Ensure the ve...

Page 11: ...ed space Follow CAN1 B149 Code latest addition and any local codes to provide enough air for combustion ventilation and proper venting Clearances must be maintained at all times from the louvred front...

Page 12: ...r solid state devices COMBUSTION AIR PROVING SWITCH The combustion air proving switch is a single pole double throw switch which is activated by differential pressures in the venter blower The switch...

Page 13: ...e readings when compared to each other A 2 voltage difference could cause as much as a 10 current imbalance OPERATION CALL A QUALIFIED SERVICEMAN FOR SERVICE OPERATIONAL CHECK 1 PILOT ADJUSTMENT a FOR...

Page 14: ...on position 3 AIR SHUTTER ADJUSTMENT See instruction label in burner compartment 4 TEMPERATURE RISE Adjust the fan pulley to get the specified temperature rise through the unit 70o F 21EC to 100o F 38...

Page 15: ...e tight on their shafts The fan pulley and motor pulley should be aligned and the belt tightened only enough to prevent slipping Replace a cracked or broken belt 5 FILTERS DISPOSABLE TYPE The air filt...

Page 16: ...burner compartment at least once per year to remove accumulated dust The fan can be removed for cleaning 9 SUMMER OPERATION A manual continuous fan switch is provided on the fan control located in the...

Reviews: