background image

April 23, 1999

Page 14

MAINTENANCE

In order to provide a maintenance history, we recommend that the owner have a maintenance
file on each unit. The following maintenance instructions are to be carried out each spring and
fall or as otherwise indicated by a qualified serviceman.

1. SET SCREWS

Check set screws on blower wheel, blower bearings, blower and motor pulleys for looseness 
on the shaft. Tighten where required. Proper torque values are available from the bearing 
manufacturer. IT IS IMPORTANT TO PERFORM THIS CHECK BEFORE INITIAL START-
UP, AFTER A RUN-IN PERIOD OF 2 TO 4 WEEKS AND THEN ON A REGULAR BASIS 
OF 4 TO 6 MONTHS.

PV shaft diameter = 3/4" (19mm): Set Screw Torque at 35 in.lb.. (4 NM).

2. FAN LUBRICATION:  No lubrication of the fan bearings is necessary.  Both ball and sleeve 

fan bearings are permanently lubricated for their life.

3. MOTOR LUBRICATION:

   

Generally motor should be lubricated with a few drops of non-

detergent SAE NO. 20 or SAE 30 oil once each year.  DO NOT over-oil or use light-weight
household oil.

4. PULLEYS AND BELTS:

  

Periodically check that the fan pulley and motor pulley are tight on 

their shafts.  The fan pulley and motor pulley should be aligned, and the belt tightened only 
enough to prevent slipping.  Replace a cracked or broken belt.

5. FILTERS - DISPOSABLE TYPE:

  

The air filter should be removed and cleaned about three 

times during the heating season.  If unit is equipped with air-conditioning, never operate 
without a filter.  Always install the filter with air-flow arrow in the proper direction.

6. FILTERS - PERMANENT TYPE:

  

If permanent, washable filters are installed, remove and 

vacuum or wash them to remove dust accumulation.  When the filter becomes worn out from 
repeated cleanings replace it with a new filter of the same size and type.  Reuse the metal 
filter clips on the new filter.

7. CONTROLS:

A.

 

Clean and recalibrate all controls.

B. Check controls for proper operation.

C. Repair or replace any controls found faulty.

D. Check all damper settings.

E. Replace blown fuses with equivalent size fuse. Failure to do so may result in damage to 

    

  the unit.

8. FURNACE INSPECTIONS and CLEANING:

 

Furnaces should be inspected once every four 

months during the heating season where the equipment is operating under normal 
conditions.

 

If the furnace is located where unusual amounts of dust or soot or other 

impurities are contained in the air, more frequent inspection is recommended.

Summary of Contents for DH-FP-PV series

Page 1: ...RETAIN INSTRUCTIONS WITH UNITAND MAINTAIN INALEGIBLE CONDITION PLEASE GIVE MODEL NO SERIAL NO WHEN CONTACTING FACTORY FOR INFORMATIONAND OR PARTS FORM PV 8 99 INDOOR POWER VENTED INDIRECT GAS FIRED HE...

Page 2: ...WALL INDIVIDUAL VENT 6 B VERTICAL INDIVIDUAL VENT 8 C OPTIONAL VERTICAL VENT TERMINAL 9 INSULATION OF SINGLE WALL VENT PIPE 9 COMBUSTION AIR 10 GAS INSTALLATION 10 DUCTWORK 11 ELECTRICAL INSTALLATION...

Page 3: ...l ENGINEERED AIR s obligations with respect to this warranty The refrigerant charge is not included in any part of this warranty ENGINEERED AIR shall not be liable to any damage to person or property...

Page 4: ...cial and Local Codes In USA a All gas piping must be installed in accordance with the National Fuel Gas Code ANSI Z223 1 latest edition The local authority having jurisdiction should be consulted for...

Page 5: ...units 1 HB HIGH BOY UNITS a Place heat section on top of fan section so the heat section is 1 2 13 behind the fan section b Carefully slide the heat section forward until the back and sides of the he...

Page 6: ...ed to locate the screws c The unit is now one piece locked together by four sheet metal screws d Pull wires from the motor wire way tube into the fan compartment and connect these wires to motor accor...

Page 7: ...ed 25 The minimum length of vent pipe is 6 One 6 diameter 90 degree elbow is equivalent to four feet of straight pipe Be sure to consider all elbows when planning the vent G All connections between th...

Page 8: ...required for clearance to combustibles 2 Prepare the lengths of flue pipe to be used Be sure to account for the position of the mounting brackets and wall thickness The flue pipe must extend beyond t...

Page 9: ...ter regulator assembly within 3 feet 1m horizontally of the vertical centre line of the regulator iv within 6 feet 1 8 of any gas service regulator vent outlet See Figure 3 for minimum clearances Size...

Page 10: ...Fan Max Column Tables may be found in CAN1 B149 codes 3 Ensure that the only large diameter vent pipe is the vent terminal itself i e the expansion must take place at the vent terminal 4 Ensure the ve...

Page 11: ...ed space Follow CAN1 B149 Code latest addition and any local codes to provide enough air for combustion ventilation and proper venting Clearances must be maintained at all times from the louvred front...

Page 12: ...r solid state devices COMBUSTION AIR PROVING SWITCH The combustion air proving switch is a single pole double throw switch which is activated by differential pressures in the venter blower The switch...

Page 13: ...e readings when compared to each other A 2 voltage difference could cause as much as a 10 current imbalance OPERATION CALL A QUALIFIED SERVICEMAN FOR SERVICE OPERATIONAL CHECK 1 PILOT ADJUSTMENT a FOR...

Page 14: ...on position 3 AIR SHUTTER ADJUSTMENT See instruction label in burner compartment 4 TEMPERATURE RISE Adjust the fan pulley to get the specified temperature rise through the unit 70o F 21EC to 100o F 38...

Page 15: ...e tight on their shafts The fan pulley and motor pulley should be aligned and the belt tightened only enough to prevent slipping Replace a cracked or broken belt 5 FILTERS DISPOSABLE TYPE The air filt...

Page 16: ...burner compartment at least once per year to remove accumulated dust The fan can be removed for cleaning 9 SUMMER OPERATION A manual continuous fan switch is provided on the fan control located in the...

Reviews: