                       18 of 27                                                                 Mar 99 R3 

 

5.

 

Curve Matching Procedure 

Turn Service Pot to high fire (approximately 3450 RPM or 57.5 Hz) for 1 minute. Adjust the 
Service Pot down very slowly until the combustion motor speed is about 3060 RPM (51 Hz). 
If the pot is adjusted below 51Hz return to high fire and attempt to lower without passing 
51Hz. Let the burner stabilize for 2 minutes, then re‐check O

2

 reading. If O

2

 has dropped to 

less  than  the  original  high  fire  O

2

  reading,  adjust  the  Curve  Matching  pot.  Adjusting  CCW 

increases the O

2

 reading by reducing the voltage to the Maxitrol modulating gas valve. The 

Curve Matching pot only changes the voltage to the gas valve; it does not affect fan speed. 

If the curve matching pot is adjusted to the fully CCW position and the O

2

 reading is still not 

within  10%  of  the  original  high  fire  O

2

  reading,  add  a  180‐ohm  2  watt  resistor  across  the 

modulating gas valve terminals; repeat above test until proper curve matching is achieved. 
(A 150‐ohm, 2‐watt resistor may have to be used if O

2

 level still does not rise to within 10% 

of original high fire O

2

 reading.) 

Switch  burner  to  low  fire  again  and  re‐check  low  fire,  both  at  0  VDC  and  2.25  VDC.  (An 
addition of a resistor above may have changed the low fire setting, if it was needed.) 

 

Lock the locking ring on the spring activated low fire adjustment screw (from step 1). Failure 
to lock it may cause the screw to vibrate loose allowing low fire gas pressure to increase. 
This can create sooting of burner parts and the heat exchanger. If the locking ring is missing, 
drop one drop of Loctite thread locker onto the brass screw threads. 

 

Series 50/M550, M650 AND ES350 (High Turndown Burner) 

These valves have only 1 low fire adjustment (spring activated low fire). 

1.

 

The combustion set up is similar to the above except there is no low fire bypass adjustment 
on the bottom of these valves. Therefore simply set up low fire by turning the manual firing 
Pot Reset Ratio to the low fire position ‐ 1250 RPM 

10 RPM 20.8 Hz. (15:1 turndown set at 

1195 RPM, 19.91 Hz.) Voltage to the series 50 valve should be near 0 volts DC. Adjust the 
spring  activated  low  fire  adjustment  at  the  top  of  the  modulating  gas  valve  (small  screw) 
until an O

2

 reading of 16.8% to 17.5% is achieved. 

2.  Lock the low fire adjustment screw as described in point 7 above and then adjust the curve 

matching pot as in point 5 above. 

 

Type ES345D‐L (High Turndown Burner) 

As this valve has 2 low fire adjustments the following procedure should be applied. 

1.

 

Bring the unit to low fire using the service firing pot fully CCW. Adjust Pot Low Fire until the 
combustion fan is turning 1250 RPM 

10 RPM (20.8 Hz). (15:1 turndown is 1195 RPM, 19.91 

Hz.) Voltage to the ES valve should be near 0 volts DC. The low fire bypass adjustment on 
this valve is under the top cover on the large port and the adjustment inside it is marked: 

Increase 



Decrease 

After  removing  the  cover,  loosen  the  locking  screw  first  before  making  adjustment.  This 
should be done at 0 VDC to the modulating gas valve terminals and the 

spring activated low 

fire brass screw

 turned fully CCW and the locking ring loosened off. 

 

Summary of Contents for DJM3

Page 1: ...D OFFICE AND FACTORY CANADIAN EASTERN FACTORY 1401 HASTINGS CRES SE CALGARY ALBERTA T2G 4C8 Ph 403 287 2590 Fax 888 364 2727 32050 W 83rd STREET DESOTO KANSAS 66018 Ph 913 583 3181 Fax 913 583 1406 11...

Page 2: ...velope which also contains the Operation Installation and Maintenance manual s This package is for copying then should either be returned to the appliance or stored in a safe place The other set is at...

Page 3: ...A DJM3 IOM 17 3 of 27 Mar 99 R3...

Page 4: ...WER OPERATION ONLY 12 MAKE BREAK RESET AND OVERRIDE 13 OR and V Override Day Operation only 13 X and Z Override Day and Night Operation 13 OPERATION 14 DAY NIGHT OPERATION 14 FAN CONTROL 14 DAMPER CON...

Page 5: ...ould be used in conjunction with the unit function sheet s and the DJ E S DG or DJX series Installation Operation and Maintenance manuals The DJM3 is designed to control only Engineered Air equipment...

Page 6: ...SA Supply air fan enable output CB1 Combustion blower motor input CB2 Combustion blower motor speed control output PV1 PV2 Pilot valve disable contact dry VFB120 Main gas valve feedback SSOV hot inpu...

Page 7: ...t TABLE 3 LIGHT LED ON 2 SEC FLASH 1 SEC FLASH INT FLASH 1 LL LOCKOUT LL BYPASS D SEN OPEN 2 PRE PURGE PP PROBLEM 3 HEAT CALL HT SW OPEN SERVICE MODE 4 IGN ENABLE FLAME FAIL 1 ON The appliance has bee...

Page 8: ...l The DJM3 did not receive a main gas valve SSOV feedback signal into terminals VFB24 or VFB120 Normal operating status OFF ADJUSTMENT POTS There are a number of setting and calibration potentiometers...

Page 9: ...rm up time 30 seconds Cool down time 60 seconds Low limit bypass 5 minutes Flame Failure 90 seconds TEMPERATURE CONTROL CALCULATED SETPOINT SPC The DJM3 is designed to be a discharge air temperature c...

Page 10: ...RESET continuous blower operation only DIP switch 3 must be on This option also requires a TE 6100 wired TABLE 8 TE 6100 Wires DJM3 Terminals Red not used GREY Wired to terminal V VIOLET Wired to term...

Page 11: ...iate wiring ROOM RESET AUTHORITY TABLE TABLE 9 Discharge Set Point Reset Ratio Pot Maximum Temp C Minimum Temp C Reset Band Width C Maximum Temp F Minimum Temp F Reset Band Width F 15 5 C 60 F 1 25 9...

Page 12: ...of the larger board just below the DIP switch block and beside Pot Reset Ratio This is a 1 watt 680 ohm resistor colours blue grey brown gold BMS reset is not truly linear Reset will usually begin at...

Page 13: ...re DIP switch 3 must be off If a thermostat or contact is closed across terminals OR and V the discharge temperature is set at 120 F 49 C When thermostat or contact is open the discharge temperature i...

Page 14: ...d as the low limit sensor If the discharge sensor resistance is too high or open circuit the DJM3 perceives a low limit fault and locks off DJM3 DAMPER CONTROL The inlet damper actuator s is enabled t...

Page 15: ...the setpoint dial will manually set the burner to any firing rate When in service mode the supply air fan may need to be activated manually Note DO NOT leave DJM3 in service mode burner will not cycle...

Page 16: ...hat smell carbon and or an excessive amount of water in the flue Care should be taken to set burners up properly Note that temperature of the air and fuel may have a great affect on the set up selecte...

Page 17: ...urn the Service Pot fully counter clockwise to achieve low fire Adjust the Low Fire Pot until the low fire speed on the combustion fan motor is 1250 RPM 10 RPM 20 8 Hz for 10 1 set up or 1195 RPM 5 19...

Page 18: ...an create sooting of burner parts and the heat exchanger If the locking ring is missing drop one drop of Loctite thread locker onto the brass screw threads Series 50 M550 M650 AND ES350 High Turndown...

Page 19: ...he valve is to be adjusted fully clockwise no bypass Series 50 M550 M650 ES350 These valves do not have high fire regulators High fire pressure is set up at the appliance regulator This series of valv...

Page 20: ...and the voltmeter The millivolt reading should be increasing At the point where it begins to fall you should stop reducing pressure and return to the high spot NOTE The fall in pressure could only be...

Page 21: ...At 3 5 O2 will appear yellow from behind the burner However if you could view it from the other side of the burner you would see blue as the flame lengthens out Low Fire At 16 O2 the flame will likel...

Page 22: ...from the tachometer sensor Hall Effect sensor that is not consistent with the combustion blower status If there is a call for heat and the combustion blower is not running the DJM3 has likely detected...

Page 23: ...the OR terminal is used the wire to terminal OR must be removed 2 Depending on which setpoint control method is used a Johnson Controls TE 6100 i Set Johnson Controls TE 6100 setpoint to 21 C ii Read...

Page 24: ...voltage is equal to the number of C maximum reset 6 Return the DIP switches to their normal position SENSOR TABLE Sensor Resistance Chart for TE 6100 960 and TE6000EA3 Table 13 C F Resistance C F Resi...

Page 25: ...n Starts after 30s Normal Operation Fan Starts after 30s 24 Vac on terminal K Equipment in Night mode fan operation is intermittent 24 Vac on terminal FS Restore power to terminal FS If burner fires f...

Page 26: ...Purge light 2 SEC FLASH Faulty DJM3 Faulty combustion fan No output from terminal CB Speed Sensor Problem Combustion fan running with 5 Vdc across terminals YS and DJM3 fuse failure or faulty DJM3 Tu...