background image

A       

 

DJM3 

IOM-17 

                       20 of 27                                                                 Mar 99 R3 

 

Pilot Set Up (Standard Burners) 

Do not

 set up pilot until you are confident the burner is operating with correct air/fuel mixture. 

Ensure the pilot tube is free of debris and blockages. On standard round burners, set pilot as 
per the following procedure. 

1.

 

Install a 10,000‐ohm resistor in series with the flame 
rod circuit. 

2.

 

Connect a DC voltmeter across the resistor. 

3.

 

The reading will be in millivolts if your meter does 
not auto scale. 

4.

 

Connect a manometer to the pilot line. 

5.

 

Run the burner on main flame for a few minutes to 
have the burner plate warm. 

6.

 

Leave the pilot on but turn the main gas off. You will 
have to jumper the DJM3 terminals PV1 and PV2 to 
do this and remove the wire from terminal VFB 120 or VFB 24 (depending on valve voltage). 

7.

 

As low pilot gas pressure can damage the ceramics, reduce the pilot gas pressure to 2.5 
inches and immediately return it to a higher pressure. This is to ensure the pilot gas regular 
responds properly. 

8.

 

Adjust the pilot valve regulator to a pressure in excess of 4.5 inches pressure. 

9.

 

Slowly reduce the pilot gas pressure while watching both the pressure and the voltmeter. 
The millivolt reading should be increasing. At the point where it begins to fall you should 
stop reducing pressure and return to the high spot. 

 

NOTE

The fall in pressure could only be as small as a couple of millivolts. This point should be 
between 4.5 and 2.5 inches pilot pressure. 

NOTE

Some smaller burners (DJ40 250,000 BTUH and smaller), may need to have a screw placed 
through the pilot air tube to reduce the amount of air to the pilot.  

 

10.

 

This reading is used to determine the adjustment that will usually give the best pilot lighting 
and proving strength. However, care must be taken to not adjust the reading for pilot gas 
pressure below 2.5 inches water column pressure or you will break the pilot ceramics. 

 

11.

 

Next, visually observe the pilot flame. It should be visible  at a minimum of 3 of the holes 
around the pilot. If the pilot cannot be seen then it is likely burning too deep into the pilot 
box. If this is occurring check that the gasket on the pilot assembly is forming a tight seal. 
Also ensure that the burner is located in the center of the burner tube. If it is mounted too 
low then too much air can flow over the top of the burner and affect the pilot.

 

 
 
 
 
 
 
 
NOTE:

 After set up is complete make sure to turn off dipswitch 5.

 

Ignition 
Control

10,000 ohms 

MV meter 

OK 

Too large a gap. Raise 
burner plate up to 
centre

Summary of Contents for DJM3

Page 1: ...D OFFICE AND FACTORY CANADIAN EASTERN FACTORY 1401 HASTINGS CRES SE CALGARY ALBERTA T2G 4C8 Ph 403 287 2590 Fax 888 364 2727 32050 W 83rd STREET DESOTO KANSAS 66018 Ph 913 583 3181 Fax 913 583 1406 11...

Page 2: ...velope which also contains the Operation Installation and Maintenance manual s This package is for copying then should either be returned to the appliance or stored in a safe place The other set is at...

Page 3: ...A DJM3 IOM 17 3 of 27 Mar 99 R3...

Page 4: ...WER OPERATION ONLY 12 MAKE BREAK RESET AND OVERRIDE 13 OR and V Override Day Operation only 13 X and Z Override Day and Night Operation 13 OPERATION 14 DAY NIGHT OPERATION 14 FAN CONTROL 14 DAMPER CON...

Page 5: ...ould be used in conjunction with the unit function sheet s and the DJ E S DG or DJX series Installation Operation and Maintenance manuals The DJM3 is designed to control only Engineered Air equipment...

Page 6: ...SA Supply air fan enable output CB1 Combustion blower motor input CB2 Combustion blower motor speed control output PV1 PV2 Pilot valve disable contact dry VFB120 Main gas valve feedback SSOV hot inpu...

Page 7: ...t TABLE 3 LIGHT LED ON 2 SEC FLASH 1 SEC FLASH INT FLASH 1 LL LOCKOUT LL BYPASS D SEN OPEN 2 PRE PURGE PP PROBLEM 3 HEAT CALL HT SW OPEN SERVICE MODE 4 IGN ENABLE FLAME FAIL 1 ON The appliance has bee...

Page 8: ...l The DJM3 did not receive a main gas valve SSOV feedback signal into terminals VFB24 or VFB120 Normal operating status OFF ADJUSTMENT POTS There are a number of setting and calibration potentiometers...

Page 9: ...rm up time 30 seconds Cool down time 60 seconds Low limit bypass 5 minutes Flame Failure 90 seconds TEMPERATURE CONTROL CALCULATED SETPOINT SPC The DJM3 is designed to be a discharge air temperature c...

Page 10: ...RESET continuous blower operation only DIP switch 3 must be on This option also requires a TE 6100 wired TABLE 8 TE 6100 Wires DJM3 Terminals Red not used GREY Wired to terminal V VIOLET Wired to term...

Page 11: ...iate wiring ROOM RESET AUTHORITY TABLE TABLE 9 Discharge Set Point Reset Ratio Pot Maximum Temp C Minimum Temp C Reset Band Width C Maximum Temp F Minimum Temp F Reset Band Width F 15 5 C 60 F 1 25 9...

Page 12: ...of the larger board just below the DIP switch block and beside Pot Reset Ratio This is a 1 watt 680 ohm resistor colours blue grey brown gold BMS reset is not truly linear Reset will usually begin at...

Page 13: ...re DIP switch 3 must be off If a thermostat or contact is closed across terminals OR and V the discharge temperature is set at 120 F 49 C When thermostat or contact is open the discharge temperature i...

Page 14: ...d as the low limit sensor If the discharge sensor resistance is too high or open circuit the DJM3 perceives a low limit fault and locks off DJM3 DAMPER CONTROL The inlet damper actuator s is enabled t...

Page 15: ...the setpoint dial will manually set the burner to any firing rate When in service mode the supply air fan may need to be activated manually Note DO NOT leave DJM3 in service mode burner will not cycle...

Page 16: ...hat smell carbon and or an excessive amount of water in the flue Care should be taken to set burners up properly Note that temperature of the air and fuel may have a great affect on the set up selecte...

Page 17: ...urn the Service Pot fully counter clockwise to achieve low fire Adjust the Low Fire Pot until the low fire speed on the combustion fan motor is 1250 RPM 10 RPM 20 8 Hz for 10 1 set up or 1195 RPM 5 19...

Page 18: ...an create sooting of burner parts and the heat exchanger If the locking ring is missing drop one drop of Loctite thread locker onto the brass screw threads Series 50 M550 M650 AND ES350 High Turndown...

Page 19: ...he valve is to be adjusted fully clockwise no bypass Series 50 M550 M650 ES350 These valves do not have high fire regulators High fire pressure is set up at the appliance regulator This series of valv...

Page 20: ...and the voltmeter The millivolt reading should be increasing At the point where it begins to fall you should stop reducing pressure and return to the high spot NOTE The fall in pressure could only be...

Page 21: ...At 3 5 O2 will appear yellow from behind the burner However if you could view it from the other side of the burner you would see blue as the flame lengthens out Low Fire At 16 O2 the flame will likel...

Page 22: ...from the tachometer sensor Hall Effect sensor that is not consistent with the combustion blower status If there is a call for heat and the combustion blower is not running the DJM3 has likely detected...

Page 23: ...the OR terminal is used the wire to terminal OR must be removed 2 Depending on which setpoint control method is used a Johnson Controls TE 6100 i Set Johnson Controls TE 6100 setpoint to 21 C ii Read...

Page 24: ...voltage is equal to the number of C maximum reset 6 Return the DIP switches to their normal position SENSOR TABLE Sensor Resistance Chart for TE 6100 960 and TE6000EA3 Table 13 C F Resistance C F Resi...

Page 25: ...n Starts after 30s Normal Operation Fan Starts after 30s 24 Vac on terminal K Equipment in Night mode fan operation is intermittent 24 Vac on terminal FS Restore power to terminal FS If burner fires f...

Page 26: ...Purge light 2 SEC FLASH Faulty DJM3 Faulty combustion fan No output from terminal CB Speed Sensor Problem Combustion fan running with 5 Vdc across terminals YS and DJM3 fuse failure or faulty DJM3 Tu...

Page 27: ...A DJM3 IOM 17 27 of 27 Mar 99 R3 UPGRADING DJM3 2 OR 3 3 to DJM3 4...

Reviews: