background image

A       

 

DJM3 

IOM-17 

                       21 of 27                                                                 Mar 99 R3 

 

Propane Gas 

Combustion set up for propane fuels for either the high turndown or the standard burner are similar to 
the above. The only modification suggested is it may be desirable to increase the oxygen settings by 1% 
to 1.5% above those for natural gas. 
 
Due  to  the  quantity  of  fuel  that  can  be  drawn  off  a  propane  tank,  it  is  often  necessary  to  equip  a 
propane fuel system with a vaporizer. The usual sign that a vaporizer is required is that the equipment 
fuel supply falls off as the line “freezes”. The following could be observed: 

 

Lack of temperature rise, 

 

Rumbling or shaking burner due to air/fuel mix, 

 

After turning the unit off for a period of time the fuel line thaws and restarting it, all appears 
to be normal. 

High turndown burners operating on propane fuel will generally exhibit the following: 

High Fire

  

At  3.5%  O

2

  will  appear  yellow  from  behind  the  burner.  However,  if  you  could 

view  it  from  the  other  side  of  the  burner  you  would  see  blue  as  the  flame 
lengthens out.  

Low Fire

  

At 16% O

2

 the flame will likely be yellow. At 17% O

2

 the flame will likely be blue 

and yellow. 

Inlet/Manifold Pressure Settings 

Manifold pressure settings that the unit was tested and clocked at in the factory are recorded on the 
unit rating plate. Any attempt to clock a unit in the field should be done with care as corrections for 
density  (altitude  and  station  pressure),  temperature,  and  for  the  meter  are  often  overlooked,  thus 
leading to an incorrect conclusion. 

Inlet gas pressures are recorded on the unit label. At high fire inlet gas pressure to the unit should not 
fall  below  6.25"  on  units  designed  for  7"  inlet  pressure.  If  design  is  for  14"  pressures  should  not  fall 
below 12". 

If design is for 11" propane gas, then inlet pressures should not fall below 10". Note that with propane 
fired units it may be necessary to equip the propane system with a properly sized vaporizer. 
 
 

 

Summary of Contents for DJM3

Page 1: ...D OFFICE AND FACTORY CANADIAN EASTERN FACTORY 1401 HASTINGS CRES SE CALGARY ALBERTA T2G 4C8 Ph 403 287 2590 Fax 888 364 2727 32050 W 83rd STREET DESOTO KANSAS 66018 Ph 913 583 3181 Fax 913 583 1406 11...

Page 2: ...velope which also contains the Operation Installation and Maintenance manual s This package is for copying then should either be returned to the appliance or stored in a safe place The other set is at...

Page 3: ...A DJM3 IOM 17 3 of 27 Mar 99 R3...

Page 4: ...WER OPERATION ONLY 12 MAKE BREAK RESET AND OVERRIDE 13 OR and V Override Day Operation only 13 X and Z Override Day and Night Operation 13 OPERATION 14 DAY NIGHT OPERATION 14 FAN CONTROL 14 DAMPER CON...

Page 5: ...ould be used in conjunction with the unit function sheet s and the DJ E S DG or DJX series Installation Operation and Maintenance manuals The DJM3 is designed to control only Engineered Air equipment...

Page 6: ...SA Supply air fan enable output CB1 Combustion blower motor input CB2 Combustion blower motor speed control output PV1 PV2 Pilot valve disable contact dry VFB120 Main gas valve feedback SSOV hot inpu...

Page 7: ...t TABLE 3 LIGHT LED ON 2 SEC FLASH 1 SEC FLASH INT FLASH 1 LL LOCKOUT LL BYPASS D SEN OPEN 2 PRE PURGE PP PROBLEM 3 HEAT CALL HT SW OPEN SERVICE MODE 4 IGN ENABLE FLAME FAIL 1 ON The appliance has bee...

Page 8: ...l The DJM3 did not receive a main gas valve SSOV feedback signal into terminals VFB24 or VFB120 Normal operating status OFF ADJUSTMENT POTS There are a number of setting and calibration potentiometers...

Page 9: ...rm up time 30 seconds Cool down time 60 seconds Low limit bypass 5 minutes Flame Failure 90 seconds TEMPERATURE CONTROL CALCULATED SETPOINT SPC The DJM3 is designed to be a discharge air temperature c...

Page 10: ...RESET continuous blower operation only DIP switch 3 must be on This option also requires a TE 6100 wired TABLE 8 TE 6100 Wires DJM3 Terminals Red not used GREY Wired to terminal V VIOLET Wired to term...

Page 11: ...iate wiring ROOM RESET AUTHORITY TABLE TABLE 9 Discharge Set Point Reset Ratio Pot Maximum Temp C Minimum Temp C Reset Band Width C Maximum Temp F Minimum Temp F Reset Band Width F 15 5 C 60 F 1 25 9...

Page 12: ...of the larger board just below the DIP switch block and beside Pot Reset Ratio This is a 1 watt 680 ohm resistor colours blue grey brown gold BMS reset is not truly linear Reset will usually begin at...

Page 13: ...re DIP switch 3 must be off If a thermostat or contact is closed across terminals OR and V the discharge temperature is set at 120 F 49 C When thermostat or contact is open the discharge temperature i...

Page 14: ...d as the low limit sensor If the discharge sensor resistance is too high or open circuit the DJM3 perceives a low limit fault and locks off DJM3 DAMPER CONTROL The inlet damper actuator s is enabled t...

Page 15: ...the setpoint dial will manually set the burner to any firing rate When in service mode the supply air fan may need to be activated manually Note DO NOT leave DJM3 in service mode burner will not cycle...

Page 16: ...hat smell carbon and or an excessive amount of water in the flue Care should be taken to set burners up properly Note that temperature of the air and fuel may have a great affect on the set up selecte...

Page 17: ...urn the Service Pot fully counter clockwise to achieve low fire Adjust the Low Fire Pot until the low fire speed on the combustion fan motor is 1250 RPM 10 RPM 20 8 Hz for 10 1 set up or 1195 RPM 5 19...

Page 18: ...an create sooting of burner parts and the heat exchanger If the locking ring is missing drop one drop of Loctite thread locker onto the brass screw threads Series 50 M550 M650 AND ES350 High Turndown...

Page 19: ...he valve is to be adjusted fully clockwise no bypass Series 50 M550 M650 ES350 These valves do not have high fire regulators High fire pressure is set up at the appliance regulator This series of valv...

Page 20: ...and the voltmeter The millivolt reading should be increasing At the point where it begins to fall you should stop reducing pressure and return to the high spot NOTE The fall in pressure could only be...

Page 21: ...At 3 5 O2 will appear yellow from behind the burner However if you could view it from the other side of the burner you would see blue as the flame lengthens out Low Fire At 16 O2 the flame will likel...

Page 22: ...from the tachometer sensor Hall Effect sensor that is not consistent with the combustion blower status If there is a call for heat and the combustion blower is not running the DJM3 has likely detected...

Page 23: ...the OR terminal is used the wire to terminal OR must be removed 2 Depending on which setpoint control method is used a Johnson Controls TE 6100 i Set Johnson Controls TE 6100 setpoint to 21 C ii Read...

Page 24: ...voltage is equal to the number of C maximum reset 6 Return the DIP switches to their normal position SENSOR TABLE Sensor Resistance Chart for TE 6100 960 and TE6000EA3 Table 13 C F Resistance C F Resi...

Page 25: ...n Starts after 30s Normal Operation Fan Starts after 30s 24 Vac on terminal K Equipment in Night mode fan operation is intermittent 24 Vac on terminal FS Restore power to terminal FS If burner fires f...

Page 26: ...Purge light 2 SEC FLASH Faulty DJM3 Faulty combustion fan No output from terminal CB Speed Sensor Problem Combustion fan running with 5 Vdc across terminals YS and DJM3 fuse failure or faulty DJM3 Tu...

Page 27: ...A DJM3 IOM 17 27 of 27 Mar 99 R3 UPGRADING DJM3 2 OR 3 3 to DJM3 4...

Reviews: