A
XES SC MANUAL
IOM-58
21 of 30
June 14 R5
DUCT MOUNTED TE-6000-EA3 TEMPERATURE SENSOR
Some applications require field installed discharge air
sensors.
The sensor strip must be parallel to the air flow. The
sensor should be mounted near the center of a straight
duct 5 to 10 feet (1500 to 3000mm) downstream of the
supply air connection to the Engineered Air unit. Avoid
installing near duct transitions or elbows.
Use twisted pair or shielded wiring. The ground shield
should be grounded only at the unit control panel end.
Protect the opposite end ground and any unused wire
with electrical tape.
When installing an Engineered Air TE-6000-EA3 duct
mounted temperature sensor, the sensor strip must be
parallel to the air flow as shown.
BEFORE START-UP
Ensure all shipping blocks, tie-down bolts, straps and blocks, etc. are removed.
Perform a Safety Shutoff Valve Leak Test as described in this manual.
START-UP CHECK LIST
Warning:
This unit is connected to high voltages. Electrical shock or death could occur if
instructions are not followed. This equipment contains moving parts that can start
unexpectedly. Injury or death could occur if instructions are not followed. All work
should be performed by a qualified technician. Always disconnect and lock out power
before servicing. DO NOT bypass any interlock or safety switches under any
circumstances.
The start-up and operation must be done in accordance with safe practices. Start-up must be performed
by qualified personnel. Complete the attached start-up record.
1
Set all associated electrical switches, controls, thermostats and main disconnect switch to
“OFF” position.
2
Close all manual valves and field piping valves.
3
Confirm that all shipping materials have been removed. See any supplemental instructions
shipped with the unit to help identify possible locations.
4
Check all bearings, drive and fan set screws for tightness.