background image

A

 

G-TRAC MANUAL 

 

IOM-24 

Page 2 

March 1999 R1

 

 

The flame relay 

(external to the G-TRAC)

 energizes the ignition transformer and pilot solenoid valve. 

 

When the pilot is established, the flame relay will power the main gas valve and shut off the spark. 

 

The G-TRAC and its associated controls maintain the discharge air temperature.  

If the rise in discharge air temperature at low fire is greater than that required to satisfy the set-point, it is 
necessary to cycle the burner on and off. The normal G-TRAC will likely cycle at about one minute intervals 
and at a 20ºF-temperature swing when a low temperature rise is required. At extra cost the G-TRAC can be 
tuned  to  "high  sensitivity"  which  causes  more  burner  cycling  but  gives  better  discharge  control  during 
conditions when only a small increase is needed in discharge temperatures. 

When higher temperature rise is required the G-TRAC will modulate the size of the flame rather than cycle 
the burner. Note that burner cycling may occur in temperatures where theory suggests modulation should be 
possible. This is caused by the mass of the heat exchanger, the time heat transfers to the air and the time for 
the discharge temperature control device to react. 

 

After a heat call is complete the combustion blower will remain in a "maintain purge” mode for 7 to 15 
minutes 

(depending on jumper selection noted later)

. If the combustion blower is running it will allow a heat 

call to start immediately without going through pre-purge. 

IV. TEMPERATURE CONTROL 

G-TRAC as a Slave to the CTRAC 

In this application there is no temperature control sensor or set point attached to the G-TRAC. The G-TRAC’s 
ability to control the firing rate is done with a 0 to 10 VDC volt signal from a CTRAC2.1 terminals "HD and B", 

(0 to 8.5 VDC on the CTRAC2 version terminal "HT and B")

. The CTRAC2.1 is the master control of the system. 

G-TRAC heat call light will be activated when about a 4.5 VDC signal is received from the CTRAC. Terminal 
HT to B are connected to D and W of G-TRAC.  Refer to C-TRAC manual also. 

 

Suggested Settings Re Hunting Problems 

 

 

C-TRAC2.1 with G-TRAC with TE 6000-960 discharge sensor – may modulate through 20 degrees. 

 

Set C-TRAC Pots 

Set G-TRAC Pots 

P3 = 6 min. as high as 9 
P6 = 5 *** 
P11 = 2 

P5 = 2 
P6 = 4 
P8 = 4 

 
C-TRAC2.1 with G-TRAC and hyper sensor – may modulate whtough 10 degrees. 
 

Set C-TRAC Pots 

Set G-TRAC Pots 

P3 = 6 min. as high as 9

P5 = 2 

P6 = 5 *** 

P6 = 4 

P11 = 2 

P8 = 4 

 
*** On C-TRAC2.1 pot 6 does not exist. 

G-TRAC as a “Stand Alone Device” 

Either the internal set point or an external set point will be used as the discharge set point. Most installations 
will use an external set point. 

The usual discharge set-point control is a Penn TE 6100-960 control 

(which is both a set point and sensor, but 

only the set point half is wired)

. The TE 6100-960 set-point device requires a cover such as T4000-264S. The 

discharge sensor is a Penn TE 6000-960 sensor located in the discharge air stream.  

Summary of Contents for G-TRAC 1.1

Page 1: ...D OFFICE AND FACTORY CANADIAN EASTERN FACTORY 1401 HASTINGS CRES SE CALGARY ALBERTA T2G 4C8 Ph 403 287 4774 Fx 888 364 2727 32050 W 83rd STREET DESOTO KANSAS 66018 Ph 913 583 3181 Fx 913 583 1406 1175...

Page 2: ...ns and Resistance Values 3 Sensor Resistance Chart for TE 6100 960 and TE 6000 960 4 Temperature Can Be Controlled By 4 VI RESET CONTROL 4 Example 1 5 Example 2 5 Example 3 5 Multiple Room Sensors 6 R...

Page 3: ...Firing 12 Low Heat Burner Firing 12 Unit Short of Temperature Rise 12 Over Delivering Air 13 Inlet Gas Pressure Low or Burner Rumbles 13 Regulator Manifold Pressure Low or Slow to Respond 13 Gas Valve...

Page 4: ...R1 ESTIMATED POT SETTINGS Use for situations where design values not available 16 Combustion Set Up 17 High Fire Combustion Set Up 17 Low Fire Combustion Set Up 17 Mid Fire Range Combustion Set Up 17...

Page 5: ...who is familiar with the control Tampering may misalign the control operation resulting in poor combustion and or poor temperature control or calibration III SIMPLIFIED OPERATION 24 V power to termina...

Page 6: ...later If the combustion blower is running it will allow a heat call to start immediately without going through pre purge IV TEMPERATURE CONTROL G TRAC as a Slave to the CTRAC In this application ther...

Page 7: ...0 85 F and often remote mounted If the TE 6100 960 is used as a set point S to SP must not be jumpered and the TE 6100 must be wired TE 6100 Wires CTRAC2 1 Terminals Violet not used sensor Blue U Oran...

Page 8: ...ature Can Be Controlled By DISCHARGE AIR CONTROL Consists of TE6000 960 duct sensor and set point often TE 6000 960 wired as above or use the internal set point pot 4 with a jumper on S to SP DISCHARG...

Page 9: ...point Ratio pot 2 Room Call Max Room Call Min 63 F 72 F Pos 4 18 81 F 45 F This will allow discharge temperature as high as 81 F If the room set point were turned up to 76 F we would reset discharge...

Page 10: ...Q and U To force a G TRAC to low fire substitute a 1000 ohm resistor for the discharge sensor and adjust the set point pot to a point that just turns the heat call light on VIII G TRAC DISCHARGE TEMPE...

Page 11: ...arge temperature It should be wired to terminals Q and U Adjust pot 1 until the heat light just shuts off This places the G TRAC in its dead band area Return the control to normal Assuming the control...

Page 12: ...ls Z and X and measure the resistance on them Reconnect the wires Compare the reading with the TE 6000 resistance chart in this document Adjust the room reset set point dial to the same value as relat...

Page 13: ...gh to drive the calculated set point below the controls setting It can also result in SA SA contacts cycling and damage the supply air motor or contactor If this is a problem 1 Disconnect all grounds...

Page 14: ...4 20 MA BMS System Position 5 75 1 40 on 0 10 VDC BMS System P8 BURNER ON OFF CONTROL BAND This sets the points at which the burner cycles on and off There is no delay off Setting this control low in...

Page 15: ...TROUBLE SHOOTING Supply Blower Not Starting G TRAC DIAGNOSTIC LIGHTS HEAT CALL PRE PURGE TIMER BURNER ENABLE COMBUS TION BLOWER OPERATING CONDITIONS OR PROBLEM DIAGNOSIS OFF OFF OFF OFF Check for 24 V...

Page 16: ...ints resets and calibration OFF ON OFF RUNNING There has been a short heat call Check for intermittent wiring electrical noise intermittent sensors set points or rapidly changing BMS Signals Shielded...

Page 17: ...cludes the main regulator and the line is not adequately sized an erratic inlet pressure will result and cause improper combustion and also burner pulsating problems Some SJ unit manifolds have RV app...

Page 18: ...f in order for the heat exchanger to warm up Voltage to and would then go to O VDC again resulting in no call for heat and the cycle will then repeat Note that some DDC or BMS panels must have a posit...

Page 19: ...pilot orifice and the depth of the pilot stub past the burner retention plate is very important see sketch below F A poor ground path can contribute to flame failure problems If this is suspected a g...

Page 20: ...lows a maintain purge time of 12 minutes plus or minus 2 minutes ESTIMATED POT SETTINGS Use for situations where design values not available If the old G TRAC is available there was a sticker inside t...

Page 21: ...inlet damper Low Fire Combustion Set Up Remove Q209 used in above step Attach G TRAC wiring from terminals RBW to gas valve Adjust discharge temperature pot or control to just bring heat light on Aft...

Page 22: ...r not calling for heat Supply fan should come on within 34 sec Yes No Normal operation If heat light comes on within 2 min of fan starting fan may shut off while burner prepares for pre purge Pre purg...

Page 23: ...IOM 24 Page i March 1999 R1...

Reviews: