Cable Management 

Cable guides can be installed on either side of the WR-
10U to groom cables from the front of each equipment 
chassis back to the wall.  A package of five cable guides 
is available as Model CG-5. 
A side plate with cable take-up reels, Model SPL-4H, can 
be added to store excess cable length being fed to 
installed equipment. The SPL-4H mounts to either side of 
the WR-10U and includes two adjustable, split reels. 

3.   DESCRIPTION 

The WR-10U (Figure 3) features welded steel, carrier-
class construction. The front of the frame provides two 
vertical rails with standard threaded hole spacing for up to 
ten rack units. Eight pairs of threaded grounding holes 
and pre-installed screws are provided on the rear 
crossbar for attachment of ground lugs. One pair of holes 
supports grounding of the WR-10U itself and the other 
seven pairs of holes support ground connections from 
installed equipment. The unpainted grounding area 
provides metal-to-metal contact with ground lug surfaces. 

 

Figure 3. WR-10U Features 

Cable Guides 

Optional cable guides with removable covers (Figure 4) 
can be attached to either side of the WR-10U frame. Up 
to ten cable guides can be installed per side. 

Side Plate with Take-up Reels 

An optional side plate, Model SPL-4H (Figure 5), provides 
two adjustable cable take-up reels. The reels are sized to 
maintain proper bend radius in fiber applications. The 

metal plate can be attached to either side of the WR-10U 
frame using the included hardware. 

 

Figure 4. Cable Guide 

 

 

4.   INSTALLATION 

The WR-10U shipping carton contains the following: 

  Pre-assembled mounting frame 

  Six (6) #12 x 1

” 

slotted hex screws, self-tapping 

  Product documentation 

  Drill template 

Installation steps are described in detail below.  

A. Mounting frame 

c

 Select an appropriate location on a wall or backboard 

to install the mounting frame. Choose a mounting 
surface and hardware that can support the combined 
weight of the mounting assembly and equipment that 
is to be installed. Mounting to a 3/4

” thick backboard 

with #12 x 1

” 

screws is recommended. Maximum 

weight holding capacity of the WR-10U is 200 lbs. 

d

 Determine the desired orientation of the ground lugs. 

The symmetrical design of the WR-10U frame allows it 
to be installed with the grounding holes facing upward 
or downward. 

e

 Tape the drill template to the wall ensuring it is level.  

The drill template provides information for multiple wall 

Threaded 
grounding holes

 

Standard threaded hole 
spacing for up to 10 rack units

 

Slide on/off cover

 

 

Figure 5. Model SPL-4H Side Plate 

 

Figure 6. Model SPL-4H Side Plate 

 

 