CCS3100
24
User Manual R0.2
P005: Discharge Pressure Warning Level (Line Warn Value):
When the supply pressure exceeds the value specified here, at the end of the time entered to the "P033 Line
Pressure Alarm Delay " parameter, the device displays the relevant warning on the screen. The protection function
can be cancelled by setting the related parameter to "0".
P006: Screw Sensor Enable (Screw Sensor):
Used to activate the use of screw pressure sensor.
P007: Low Level Screw Pressure (Min Screw Press.):
If the measured screw pressure is equal to or higher than the value entered to this parameter, when the run
command is received when the device is in stop mode, the compressor is not started and the system waits for the
pressure value to decrease. When the screw pressure drops below this value, the running process continues.
P008: Screw Pressure Fail Alarm (ScrewPress Alarm):
When the screw pressure reaches the value specified here, the device switches to fault mode at the end of the time
entered to the "P034 Screw Pressure Alarm Delay" parameter. The protection function can be cancelled by setting
the related parameter to "0".
P009: Screw Pressure Warning Alarm (ScrewPress Warn):
When the supply pressure exceeds the value specified here, at the end of the time entered to the "P034 Screw
Pressure Alarm Delay " parameter, the device displays the relevant warning on the screen. The protection function
can be cancelled by setting the related parameter to "0".
P010: Pressure Unit (Pressure Unit):
Determines the pressure unit that the device measures in, displays on the screen and checks. Can be selected as BAR
or PSI.
P011: Pressure Difference Fail Alarm (DeltaPress Alarm):
If the difference between the screw pressure and the line pressure is above this value, the device switches to fault
mode with the message " DeltaPress Alarm" at the end of the "P035 Delta Pressure Alarm Delay" period.
P012: Pressure Difference Warning Alarm (DeltaPress Warn):
If the difference between the screw pressure and the line pressure is above this value, the message " DeltaPress
Warn" is displayed on the screen at the end of the " P035 Delta Pressure Alarm Delay" period.
P013: Difference Pressure Limit Value (SufficiencyPress):
When the screw pressure value reaches the value entered to this parameter, the pressure difference and warning
functions are activated. Relevant controls are not made at pressure values below the value entered to these
parameters.
P014: Standard Pressure Load (Stand.Press Load):
Used to quickly load standard pressure values. The value entered to this parameter, the automatically changing
parameters and the formulas of the changing values are given in the table below.
Affected Parameter
Affection Status
P002: Switch to Idle Pressure (Switch to Idle Press.): = P014
P003: Switch to Load Pressure (Switch to Load
Press.):
= P014 – 1.5 BAR
P004: Line Pressure Fault Value (Line Press Fault):
= P014 + 1.0 BAR
P005: Line Pressure Warning Value (Line Press
Warning):
= P014 + 0.5 BAR
P008: Screw Pressure Fault Value (Screw Press
Fault):
= P014 + 1.1 BAR