CCS3100
29
User Manual R0.2
P071: Input Delay 8:
After the relevant input is active, at the end of the time value entered to this parameter, the device takes the input
as active.
P072: Input Contact Type 8:
The contact type of the relevant input, can be selected as NO (normally open) or NC normally closed.
2.2.4 Digital Output Parameters
Functions That Can Be Assigned to Outputs:
The functions that can be assigned to the outputs and their explanations are as follows.
None:
No function is assigned to the related digital output. If no connection has been made, it is recommended to
set it as "None".
Main Con.:
The output function that the Main Contactor will be connected.
Star Con.:
The output function that Star Contactor will be connected.
DeltaCon.:
The output function that the delta contactor will be connected.
LoadValve:
The output function that the load valve will be connected.
Alarm:
In case of any fault, this output becomes active.
Warning:
In case of any warning, this output becomes active.
Alarm+Warn:
In case of any fault or warning, this output becomes active.
Fan:
The output function where the Fan Contactor will be connected.
OnLoad:
The output is active when the compressor is running and the solenoid valve is active.
Idle:
The output is active when the compressor is running and the solenoid valve is passive.
Running:
When the compressor motor is running, this output is active.
Stopping:
When the compressor motor stops, this output is active.
Horn:
The output to which horn, siren or similar warning equipment will be connected.
Dryer-Time:
The output related to the dryer. See “Application note Dryer Functions”.
Dryer-T2:
The outp
ut related to the dryer. See “Application note Dryer Functions”.
RSS Active:
This output is activated only when the starting source is selected as Modbus, Digital input or
Digital input.
T.LowAlarm:
This output is activated when the screw oil temperature drops below the value entered to the "P124
Temperature 1 Low Alarm " parameter.
T.Up Alarm:
This output is activated when the screw oil temperature rises above the value entered to the "P122
Temperature 1 High Alarm " parameter.
T.Low Warn:
This output is activated when the screw oil temperature drops below the value entered to the "P125
Temperature 1 Low Warn" parameter.
T.Up Warn:
This output is activated when the screw oil temperature exceeds the value entered to the "P123
Temperature 1 High Warning" parameter.